Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T03CM05695
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2006 | ELECTRIC - PROGRESS | Approved | ||
01/05/2006 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*OK NEW CKT'S TO PROJECTORS ( # 8 40 AMP) OK TO USE BUILDING FOR JAN 7 2006 EVENT ONLY NOTE: MAKE SURE THERE IS NO OPEN WIRING IN AREA'S USED FOR EVENT. |
|
01/04/2006 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROVIDE PROPER CKT SIZE (#8) AND OVERCURRENT (40) TO PROJECTORS 2. CHECK BOX FILL FOR CONDUCTORS, APPEARS TO BE OVERFILLED SOME LOCATIONS. 3. WHERE YOU HAVE MORE THAN THREE CONDUCTORS IN RACEWAY-CHECK NEC 310.15 4. SECURE AND STRAP ALL RACEWAYS AS REQUIRED AND CLOSE ALL UN-USED OPENINGS IN EQUIPMENT. 5. READ THROUGH, NEC 540 AND 640 TO VERIFY PROPER INSTALLATION OF EQUIPMENT 6. PROPERLY IDENTIFY PANELS AND DISCONNECTS. |
|
12/29/2005 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :*CLOSE OFF ALL J-BOX'S AND OPEN WIRING IN ANY AREA THAT ARE ACCESSIBLE TO THE PUBLIC INSTALL ALL DOORS ON AREAS THAT ARE NOT TO BE ACCESSED TO PUBLIC EMERGENCY LIGHTS NORTHEAST ALLEY EXIT AND EXTERIOR ELECTRICAL ROOM NEED TO BE WORKING |
|
12/23/2005 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :*WALKED THROUGH W/RAY NOTE: DON'T FORGET GROUNDING AND BONDING FOR GENERATOR | |
12/22/2005 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :*LOOKED AT BASEMENT LOBBY AND BATH AREA NOT READY FOR COVER AT THIS POINT | |
12/21/2005 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :*OK 2ND FLOOR LOBBY & BATH CEILING AREA AFTER SLACK WIRES INSTALLED. LOOKED AT 2ND FLOOR LOBBY AND BATH CEILING AREA NEED SLACK WIRES ON TRACK LIGHTING EVERYTHING ELSE LOOKED OK |
|
12/20/2005 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL PROPER SIZE FUSES IN A.C. DISCONNECTS 2. STRAP CONDUIT & FLEX AS REQUIRED. 3. REMOVE EMT TRIPPING HAZARD 4. GROUND ALL DISCONNECT ENCLOSURES 5. IDENTIFY RTU'S @ UNIT AND PANEL |
|
12/19/2005 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :*PANEL FEEDER OK "TECH" "EM" "TECH" "SA" "EMB" "5B" "B" |
|
12/16/2005 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :*OK PANEL 22 OK" DBA" OK TO CLOSE |
|
12/14/2005 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK TO ENERGIZE TRANSFORMER "TI" AND "T2" AND SWITCHBOARD - "DPA AND "DPE" NOTE: INSTALL GROUNDING ELECTRODE CONDUCTOR AND BONDING JUMPER CONDUCTOR UNDER SAME LUG - IN TRANSFORMER "TI" |
|
12/13/2005 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* PROGRESS IS GOOD NO INSPECTIONS READY TODAY |
|
12/12/2005 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* OK PANEL "CA" AND "CB" IN CATWALK - TRANSFORMER "T2" HAS UNDERSIZE EQUIPMENT GROUND (NEED 40) TRANSFORMERS "T3" OK TRANSFORMER "T1" HAS UNDERSIZE LOAD SIDE EQUIPMENT GROUND |
|
12/07/2005 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* - PANEL "BL" IS OK TO ENERGIZE - PANEL "2" IS OK TO ENERGIZE - PANEL "MECH" HAS UNDERSIZED EQUIPMENT GROUND - PANEL "MECH" OK TO ENERGIZE FOR THE PURPOSE OF BLOWING OUT DUCTS FOR SHORT PERIOD - THEN SHUT DOWN - PROVIDE NEWLY APPROVED ELECTRICAL PLANS - NEED TO REMOVE OBSTRUCTION IN FRONT OF PANELS "PL" & "Z" - NEED TO CHECK ALL FEEDERS AND EQUIPMENT GROUNDS - NEED TO TIGHTEN ALL BONDING BUSHINGS AND LUGS |
|
11/22/2005 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :*PROGRESS GOOD, TALKED WITH ROB ABOUT SERVICE. |