Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM05695
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1. FIRE DAMPERS ORGAN SUPPLY & RETURN CAN BE RESET & LINKAGE REPLACED W/ACCESS COVER IN DUCT AS LOCATED. |
|
08/18/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* ACCESS PANELS IN DUCTS W/FIRE DAMPERS MUST BE LARGE ENOUGH AND LOCATED CLOSE ENOUGH TO ALLOW LINKAGE TO BE REPLACED. |
|
08/08/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* AUX. DRAIN PANS ON 1ST FLR. FAN COILS -- SENSORS BEING LOCATED ON FAN COILS IN ATTIC PLENIUM. |
|
06/28/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) WHEN ALL OFFICE PAPERWORK HAS BEEN APPLIED FOR A MECH TEMP C OF O IS OK |
|
03/30/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
02/17/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* INSP. DONE 2/15 NO NEED FOR INSP TODAY |
|
02/15/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TEMP C OF O UNDER STAGE DRESSING ROOMS |
|
12/30/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
12/06/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* FAN COILS - AUX. DRAIN PANS AND PIPING? ATTIC INSUL. PLENUM NOTED GLASS? IT NOT ALL EDGES OF FOIL MUST BE COMPLETELY SEALED. |