Permit: T03CM05695

Parcel: 117120340


Addresses:

17 W CONGRESS ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM05695

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/28/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
1. FIRE DAMPERS ORGAN SUPPLY & RETURN CAN BE RESET & LINKAGE REPLACED W/ACCESS COVER IN DUCT AS LOCATED.
08/18/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
ACCESS PANELS IN DUCTS W/FIRE DAMPERS MUST BE LARGE ENOUGH AND LOCATED CLOSE ENOUGH TO ALLOW LINKAGE TO BE REPLACED.
08/08/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
AUX. DRAIN PANS ON 1ST FLR. FAN COILS -- SENSORS BEING LOCATED ON FAN COILS IN ATTIC PLENIUM.
06/28/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) WHEN ALL OFFICE PAPERWORK HAS BEEN APPLIED FOR A MECH TEMP C OF O IS OK
03/30/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/17/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
INSP. DONE 2/15 NO NEED FOR INSP TODAY
02/15/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) OK TEMP C OF O UNDER STAGE DRESSING ROOMS
12/30/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
12/06/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
FAN COILS - AUX. DRAIN PANS AND PIPING?
ATTIC INSUL. PLENUM NOTED GLASS? IT NOT ALL EDGES OF FOIL MUST BE COMPLETELY SEALED.