Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM05695

Parcel: 117120340


Addresses:

17 W CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM05695

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2006 ELECTRIC - FINAL Approved
06/15/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINAL APPROVAL SUBJECT TO CONDITIONS LISTED BELOW.
1. PIPE ORGAN TO BE INSTALLED UNDER SEPARATE PERMIT
2. FINAL APPROVAL OF ALL UNLISTED/UNTESTED EQUIPMENT PREVIOUSLY MENTIONED IN THIS REPORT THROUGH RANDY SCHULER.
06/07/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PROVIDE PAPERWORK FOR ALL SYSTEM AS PREVIOUSLY REQUESTED.
05/30/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOND T-1, T-2, T-3 PER NEC 250.6, NEC 250.30
2. SIZE TRANSFORMER LOAD SIDE RACEWAY BONDING CONDUCTOR PER NEC 250.66
05/25/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
05/16/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK MECHANICAL PLATFORM CORRECTIONS.
05/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
FRANK WINKLER - CONCORD - REQUESTED CHARLIE FOR TUESDAY AM -- KELLEY WILL BE HERE.
DENIED -- NO ELECT ON SITE, NO KEYS TO ALARM RM,
NO WRITTEN INFORMATION ON STAGE SYSTEMS.
05/09/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ELECT. CONTRACTOR NOT ON SITE
CONCORD SUPERVISOR WILL RECALL INSPECTION
TALKED TO CONCORD SUPERVISOR JEFF BREWER AND HE WILL RECALL.
JEFF BREWER 419-1638
04/19/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CORRECTIONS IN PROGRESS -- FINISH CORRECTIONS FOR GENERATOR, MECHANICAL PLATFORM, AND SERVICE ROOM.
THEN WE WILL MOVE TO BASEMENT, ALSO, STILL NEED TESTING APPROVAL FOR STAGE SYSTEMS.
04/18/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
CORRECTIONS IN PROGRESS - CONTRACTOR NOT ON SITE.
*NOTE: NEED KEYS TO ALARM PANEL, FINISH ALL CORRECTIONS TO THIS POINT, THEN HAVE BASEMENT AREA READY FOR INSPECTION.
04/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR GENERATOR.
1. GENERATOR TRANSFER SWITCH DOES NOT SWITCH NEUTRAL - REMOVE BONDING JUMPER AT GENERATOR NEC 250.24 (A)(5) - NOT A SEPARATELY DERIVED SYSTEM.
2. REMOVE PAINT AND TIGHTEN ALL SCREWS FOR GROUNDING CONNECTIONS IN TRANSFER SWITCH AND DISCONNECT NEC 250.4
3. PROVIDE LABELS FOR TRANSFER SW AND DISCONNECT.
PREVIOUS CORRECTIONS ONGOING, NEED KEY FOR ALARM PANELS
04/11/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. AT MOTOR CONTROL PANEL, INSTALL SAME SIZE GROUNDS UNDER SAME TERMINAL NEC 110.
2. BOND WATER TO "M.C.C" AND I COULD NOT FIND GROUND RODS AND #4 CU G.E.C FOR THEM (PER PLAN)
3. PROVIDE WORKING SPACE IN FRONT OF PANEL "MP" PER NEC 110.26 AND IDENTIFY PANEL AS "MP"
4. BOND PANEL "MP" TO CHILLER PIPING (PER PLAN) WILL CONTINUE NEXT INSPECTION -- GENERATOR, REMAINDER OF MECHANICAL PLATFORM, SERVICE ROOM.
04/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR ELECTRICAL ROOM AND MECHANICAL PLATFORM
1. THERE IS OBJECTIONABLE CURRENT ON FEEDER EQUIPMENT GROUNDS AT SERVICE SECTION AND SECTIONS "DPA/DPB" - NEC 250.6
2. FEEDER SET FROM GENERATOR NEEDS TO BE WIRED INTO DISCONNECT PER PLAN AND IDENTIFY DISCONNECT
3. IDENTIFY ALL EMERGENCY ENCLOSURES NEC 700.9 (A)
4. EMERGENCY WIRING TO BE SEPARATED FROM OTHER WIRING PER NEC 700.9 (B)
5. HOUSE DIMMER PACK, AND ALL EQUIPMENT SUPPLYING EMERGENCY LOADS NEED TO BE LISTED FOR EMERGENCY CIRCUITS NEC 700.3
6. ELECTRICAL ROOM AND MECHANICAL PLATFORM INSPECTION WILL CONTINUE NEXT TRIP.
04/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR ELECTRICAL ROOM AREA
1. NEED SIGN AT SERVICE PER NEC 701.9 (A) (B)
2. IDENTIFY FIRE ALARM ENCLOSURES NEC 760.10
3. CORRECTLY IDENTIFY ALL SERVICE, MAIN, AND BRANCH CKTS.
4. IDENTIFY EMERGENCY CKT ENCLOSURES NEC 700.9 (A)
5. INSPECTION TO CONTINUE.
04/03/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR STAGE AREA SYSTEMS
1. PLEASE PROVIDE DOCUMENTATION THAT THE FOLLOWING SYSTEMS HAVE HAD THIRD PARTY TESTING AND OR UL APPROVALS PERFORMED ON THEM AS A SYSTEM PER NEC 110.3 REQUIREMENTS BOTH (A) AND (B). LABELS, IF ANY ARE IDENTIFIED FOLLOWING SYSTEM "NAME".
1. "VORTEK SYSTEM" - NO LABELS ON ANY EQUIPMENT USED AS THE LIFT SYSTEM ON STAGE/LIGHTING, SCENES, ETC.
2. "SKJONBERG SYSTEM" - ENCLOSED INDUSTRIAL CONTROL PANEL UL #BH-642502 USED FOR LIFTING LIGHT RACK IN FRONT OF STAGE.
3. "PCI LIGHTING CONTROL SYSTEM" - ENCLOSED ENERGY MANAGEMENT EQUIPMENT UL #2CFO/E222633 USE FOR CUE LIGHTING SYSTEM.
4. "STAGECRAFY SYSTEMS INC" - ENCLOSED INDUSTRIAL CONTROL PANEL UL #BE651737 USED AS COMPANY SWITCH (2) 400 AMP (2) 200 AMP
5. "SENSOR DIMMING SYSTEM" UL LABEL #36C7 USED FOR DIMMING LIGHTING - HAS EMERGENCY LIGHTING RAN THROUGH IT.
6. "SERAPID" UL #A-1542 AND RITTAL #AE1180? USED TO RAISE AND LOWER STAGE.
7. MAY ALSO NEED SAME FOR PIPE ORGAN ONCE INSTALLED.
03/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR STAGE AREA
*NOTE - SYSTEMS TO BE APPROVED AS A "WHOLE"
1. REMOVE ALL DEBRIS AND COMBUSTIBLE MATERIALS FROM ALL PANELS.
2. PROVIDE LISTING OR FIELD EVALUATION FOR ALL EQUIPMENT VORTEK SYSTEM, SERAPID SYSTEM, COMPANY SWITCHES, LIFT (LIGHTING) SYSTEM, CUE LIGHT SYSTEM ETC,
STAGE AREA INSPECTION TO BE CONTINUED.
03/30/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED TO PROVIDE INFORMATION FOR VORTEK SYSTEM
UL LISTINGS, PERFORMANCE TESTING ETC.
03/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR VORTEK SYSTEM @ CATWALK
1. CHECK THAT EMERGENCY LIGHTING IS WORKING CORRECTLY.
2. PROVIDE LISTING INFORMATION FOR ALL VORTEK SYSTEM
3. GROUND GUTTERS, ENCLOSURES
4. CHECK FOR KO'S MISSING IN ENCLOSURES.
WILL CONTINUE INSPECTION NEXT VISIT.
03/28/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PARTIAL FINAL
IN CONCESSION AND AUDITORIUM AREAS
03/21/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
IN CONCESSION AREA
1. I NEED FIRE DOOR COMPLETE AND WORKING SO I CAN TEST IT
2. REMOVE TEMP. WIRING AND SECURE/SUPPORT LOW VOLTAGE WIRING IN CEILING.
3. CHECK GFI IN JANITOR CLOSET AND IDENTIFY ICE MACHINE DISCONNECT.
4. CHECK ABOVE BATHROOMS FOR PROPER RACEWAY SUPPORT AND GROUNDING @ DISCONNECTS.
03/16/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK PARTIAL FINAL BASEMENT LOUNGE AREA
2. NEED TO FINISH CORRECTIONS IN MECHANICAL BASEMENT AREA
3. STILL NEED TO GROUND ALL LIGHT FIXTURES EVEN IN PARTIALLY APPROVED AREAS.
03/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
MECHANICAL BASEMENT AREA INSPECTION ONLY
1. INSTALL K.O BLANKS AS NEEDED
2. REMOVE ALL TEMP WIRING
3. PROPERLY SECURE/SUPPORT LOW VOLTAGE & WIRING
4. IDENTIFY PANEL DIRECTORY'S
5. PROVIDE PERMANENT POWER FOR CLIMATE CONTROL PANEL
6. PROVIDE BUSHING FOR #4 AND LARGER WIRE AND GROUND J-BOXES
7. CHECK ACCESS TO J-BOXES
03/13/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PARTIAL FINAL EXTERIOR MAIN ENTRY AREA
BOTH BASEMENT AREAS NEXT INSPECTION
REMOVE TEMP LIGHTING CONDUCTORS ABOVE ALL CEILINGS
03/10/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PARTIAL FINAL TECH BOOTH, BALCONY, FOYER
*NOTE*
NEXT INSPECTIONS WILL BE BOTH BASEMENT AREAS AND EXTERIOR TICKET ENTRY AREA.
03/09/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ELECTRICAL CONTRACTOR NOT ON SITE/NO INSPECTION CALLED IN FOR TODAY.
*NOTE TO ELECTRICAL CONTRACTOR*
ALTHOUGH WE HAVE BEEN MOVING THROUGH AREAS WITH PARTIAL FINAL APPROVALS, THE GROUNDING OF CUSTOM MADE LIGHT FIXTURES THROUGHOUT THE BUILDING STILL MUST BE COMPLETED EVEN IN PARTIALLY APPROVED AREAS.
LIGHTING FIXTURES MUST BE GROUNDED AS REQUIRED BY 2002 NEC 410-SECTION V
03/07/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK REAR ALLEY
OTHER AREAS IN PROGRESS -
LIGHTING FIXTURES IN ALL AREAS NEED TO BE GROUNDED
03/03/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) GO THROUGH BASEMENT MECHANICAL AREA, REMOVE ALL TEMPORARY CIRCUITS, IDENTIFY PANEL DIRECTORIES, CLOSE OPEN BOXES, SECURE ALL CONDUITS AND CABLES ETC... THIS AREA NOT READY FOR INSPECTION. DO THE DAME FOR REAR ALLEY, AND OTHER AREAS WE WALKED THROUGH
03/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) INSPECTION FOR TECH BOOTH AND BALCONY AREA: GROUND FIRE ALARM ENCLOSURE AND REMOVE DISCARDED OBJECTS/MATERIAL
2) BRANCH CKT CONDUCTORS AND RACE WAYS FROM DIMMER PACK ARE UNDER SIZED
3) IDENTIFY CONTACTOR DISCONNECT
4) INSTALL BUSHING FOR #4 AND LARGER CONDUCTORS
BALCONY AREA:
1) GROUND LIGHT FIXTURES
2) PROVIDE BARRIER IN FLOOR BOXES FOR ELECTRICAL/DATA SEPERATION
3) HAVE 2 OUTLET NOT INSTALLED
03/01/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE ALL MAJOR EQUIPMENT OPEN AND ABLE TO BE DEENERGIZED FOR INSPECTION, ALSO CHECK ALL WIRE FILL, CONDUCTOR DERATING, GROUNDING CONNECTIONS, K.O. BLANKS, PANEL DIRECTORY, CONDUIT & FLEX STRAPPING, ACCESS TO J-BOXES, ETC. AND PROVIDE PLANS FOR TECH BOOTH
MAKE SURE LIGHTING FIXTURES ARE GROUNDED
02/28/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PARTIAL FINAL FOR FOLLOWING AREAS
1. ROOFTOP
2. MAIN CATWALK
3. 2ND LEVEL BALCONY LOUNGE, BAR AREA AND RESTROOMS
*NOTE*
NEXT INSPECTION WILL CONSIST OF TECH BOOTH AREA AND REMAINDER OF 2ND LEVEL - PLEASE GO THROUGH IN ADVANCE
02/27/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*CORRECTIONS IN UPPER LEVELS STILL IN PROGRESS
02/24/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR MAIN CATWALK AREA
1. EMERGENCY LIGHTING NOT WORKING
2. MAKE SURE PANEL DIRECTORY'S ARE MARKED CORRECTLY
3. INSTALL BOX LOVERS AS NEEDED
02/23/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*OK ROOFTOP AREA FINAL
NEED PROPER SIZE DIMMERS FOR LIGHTING FIXTURES
TIGHTEN LOOSE RECEPTACLES AND BRING BOXES FLUSH TO SURFACE WHERE SURFACE IS COMBUSTIBLE NEC 314.20
FLEXIBLE CORDS FOR TRANSFORMERS ABOVE SUSPENDED CEILING NEC 400.8 ( 5)
INSURE THAT WALL SCONES AND CHAND, HAVE PROPERLY CONNECTED EQUIPMENT GROUND NEC 410.17
INSURE PANEL DIRECTORY IS CORRECTLY IDENTIFIED NEC 408.4
02/22/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
02/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
*NOTE* INSPECTION FOR BASEMENT AREA ONLY
1. IN GENERAL, THE WIRING IS INCOMPLETE AND DOES NOT MEET MINIMUM CODE REQUIREMENTS. SOME VIOLATIONS OBSERVED ON THIS INSPECTION INCLUDE - ENCLOSURES NOT PROPERLY GROUNDED, ENCLOSURES SIZED INCORRECTLY, ENCLOSURES NOT ACCESSIBLE, UNACCEPTABLE WIRING METHODS IN DAMP, WET LOCATIONS, LACK OF GFI PROTECTION FOR PERSONNEL. SEAL OFF FITTING FOR SUMP RACEWAY, LACK OF ILLUMINATION FOR EQUIPMENT ETC, ETC
THIS AREA ALSO FEEDS ALL OTHER AREAS OF SYSTEMS FOR BUILDING AND MSUT BE INSPECTED SYSTEMATICALLY.
ALSO, INSPECTION IS CUT SHORT TODAY BECAUSE OF TIME LIMITATIONS AND INCOMPLETE WORK IN THIS AREA.
02/16/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ALSO, ON A WALK THROUGH OF THE BASEMENT AREA THE WIRING IS INCOMPLETE, SOME CKT'S ARE NOT WORKING PROPERLY, AND APPEARS TO BE CODE VIOLATIONS
02/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*PROVIDE MINIMUN WORKING CLEARANCE FOR ALL ROOF TOP EQUIPMENT NEC 110.26
INSTALL IN USE TYPE RECEPTACLE COVERS ON ROOF NEC 406.8
PROVIDE DISCONNECTING MEANS FOR MOTERO EF-1 NEC 430.109,102 (B)
RE REIN EMT TO REDUCE TRIPPING HAZARD NEC. 110.26 TO AHU -Z
AHU J-BOX NEEDS TO BE PROPERLY GROUNDED AND CLEANED UP NEC. 250.148 (A), NEC 725.6
INSTALL AUDIO ANTENNA CABLE PER NEC 820
AT FEEDER JUNCTION AREA, GROUND ALL GUTTERS AND ENCLOSURES AND MAKE SURE I.D LABELS DO NOT HINDER COVER REMOVAL, ALSO TIGHTEN ALL RACEWAY FITTINGS.
TIGHTEN BOND SCREW IN CUIL & CUZ DISCONNECTS
NEED SERVICE OUTLET FOR AUH-3 NEC 210.63
INSTALL ALL COVERS,K O BLANKS ETC, AND SEAL OFF UNUSECD RACEWAYS
SEALL ALL ROOF PENETRATIONS
SECURE HPU2 & HPU3 DISCONNECTS
SECURE ALL FLEX WITHIN 12" OF TERMINATION AS REQUIRED
NO FURTHER INSPECTIONS UNTIL ROOF IS APPROVED
DISCONNECT HPI & HPE ARE NOT GROUNDED
12/30/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245$ OK TO OCCUPY BUILDING FOR THE PURPOSE OF DEC 31 ST CELEBRATION ONLY
PLEASE CALL IN FINAL INSPECTIONS AS WORK BECOMES COMPLETED. MAKE SURE THERE IN NO OPEN WIRING IN AREAS ACCESSIBLE TO THE PUBLIC