Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: TC-COM-1023-02505
Permit Details
Apply Date:
10/23/2023
Applicant:
adam davis
Description:
This for the construction of a new Group I-2 Institutional - Condition 2, Type I-B Construction, 4 Story In-Patient Rehabilitation Hospital at 355 N. Wilmot Road, Tucson. This will be for the Building Permit connected with the civil and rezoning of the site for Account No. TD-DEV-0623-00283 being currently reviewed.
Permit Reviews
Permit Number - TC-COM-1023-02505
Permit Status: Issued
Permit Description: This for the construction of a new Group I-2 Institutional - Condition 2, Type I-B Construction, 4 Story In-Patient Rehabilitation Hospital at 355 N. Wilmot Road, Tucson. This will be for the Building Permit connected with the civil and rezoning of the site for Account No. TD-DEV-0623-00283 being currently reviewed.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/30/2023 | COMMERCIAL REVIEW - FULL v.1 | 11/30/2023 | REQUIRES RESUBMIT |
| 12/22/2023 | COMMERCIAL REVIEW - FULL v.2 | 01/23/2024 | REQUIRES RESUBMIT |
| 07/16/2024 | COMMERCIAL REVIEW - FULL v.1 | 08/16/2024 | REQUIRES RESUBMIT |
| 08/29/2024 | COMMERCIAL REVIEW - FULL v.2 | 10/02/2024 | APPROVED |
| 10/10/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 10/11/2024 | APPROVED |
| 05/15/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 05/22/2024 | APPROVED |
| 03/04/2024 | RESTAMP - COMMERCIAL v.1 | 03/05/2024 | APPROVED |
| 10/02/2024 | RESTAMP - COMMERCIAL v.1 | 10/02/2024 | APPROVED |
| 12/12/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 12/18/2024 | APPROVED |
| 01/25/2024 | COMMERCIAL REVIEW - FULL v.3 | 03/04/2024 | APPROVED |
| 12/11/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 12/18/2025 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-COM-1023-02505
Permit Status: Issued
Permit Description: This for the construction of a new Group I-2 Institutional - Condition 2, Type I-B Construction, 4 Story In-Patient Rehabilitation Hospital at 355 N. Wilmot Road, Tucson. This will be for the Building Permit connected with the civil and rezoning of the site for Account No. TD-DEV-0623-00283 being currently reviewed.
Total Outstanding Activity Conditions - 10
| Date | Name |
|---|---|
| 01/30/2024 | SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED. |
| 01/30/2024 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
| 01/30/2024 | SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED. |
| 01/30/2024 | SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED. |
| 01/30/2024 | SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED. |
| 01/30/2024 | Masonry Inspection Report submittal review is required. |
| 01/30/2024 | SPECIAL INSPECTION FOR MEDICAL GASES IS REQUIRED. |
| 01/30/2024 | SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED. |
| 01/30/2024 | SPECIAL INSPECTION FOR STRUCTURAL WELDING IS REQUIRED. |
| 01/30/2024 | SPECIAL INSPECTION FOR WELDING IS REQUIRED. |
Conditions
Permit Number - TC-COM-1023-02505
Permit Status: Issued
Permit Description: This for the construction of a new Group I-2 Institutional - Condition 2, Type I-B Construction, 4 Story In-Patient Rehabilitation Hospital at 355 N. Wilmot Road, Tucson. This will be for the Building Permit connected with the civil and rezoning of the site for Account No. TD-DEV-0623-00283 being currently reviewed.
| Date | Description | Comments |
|---|---|---|
| 03/05/2024 | The Contractor you have added to your permit cannot be verified. Please contact staff to have the ROC number added to the account. | |
| 10/30/2023 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 10/30/2023 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. | |
| 12/18/2024 | ||
| 05/22/2024 | Stair Designs must be submitted and approved prior to... | |
| 12/15/2025 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: Issued
Permit Number: TC-COM-1023-02505
Permite Description: This for the construction of a new Group I-2 Institutional - Condition 2, Type I-B Construction, 4 Story In-Patient Rehabilitation Hospital at 355 N. Wilmot Road, Tucson. This will be for the Building Permit connected with the civil and rezoning of the site for Account No. TD-DEV-0623-00283 being currently reviewed.
Total Outstanding Inspections - 24
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2024 | COT - HCPL - Plumbing Progress | N/A | Partial Pass | Main drain on South of building B. |
| 10/30/2024 | COT - HCBU - Preslab | N/A | Partial Pass | Level One, West half. |
| 02/06/2025 | COT - HCPL - Plumbing Roof Drains | N/A | Partial Pass | Level Three, Area B. |
| 06/12/2024 | COT - HCBU - Excavation/Rebar/Zoning | N/A | Partial Pass | East side to large elevator, and small elevator. |
| 04/28/2025 | COT - HCPL - Plumbing Intermediate | N/A | Partial Pass | 4th Floor, area A, DWV. |
| 11/26/2024 | COT - HCBU - Exterior Clips/Sheathing | N/A | Partial Pass | Levels One through Four, North wall. |
| 04/17/2025 | COT - HCBU - Framing | N/A | Partial Pass | |
| 06/06/2025 | COT - HCEL - Electrical Above Ceiling | N/A | Re-inspection required | Partial Inspection for Level Two: Complete low voltage wiring. |
| 02/25/2025 | COT - LCEL - Electrical Underground | N/A | Partial Pass | Generator conduits. |
| 01/29/2025 | COT - HCBU - Interior Shear Bracing | N/A | Not Ready | wanted Fire wall. |
| 09/24/2024 | COT - HCEL - Electrical Intermediate | N/A | Partial Pass | Main duct banks underslab |
| 04/01/2025 | COT - HCME - Mechanical Progress | N/A | Partial Pass | 2nd floor HVAC |
| 10/14/2024 | COT - LCPL - Yard Water Line | N/A | Canceled | |
| 08/04/2025 | COT - HCME - Kitchen Hood | N/A | Canceled | |
| 08/01/2025 | COT - HCBU - Building Above Ceiling | N/A | Partial Pass | Level one. |
| 12/04/2024 | COT - HCBU - Firewall/Fire Barrier/Firestop | N/A | Partial Pass | 12/3/2024 4th floor monoco fire proofing approved. Pending columns and beams at stairways. RFI on angle bracing for coverage. |
| 07/30/2024 | COT - HCEL - Grounding/Bonding | N/A | Partial Pass | 7/30/24: ufer for northwest corner property okay to place concrete |
| 11/21/2025 | COT - HCEL - Electrical Final | N/A | Partial Pass | Level Three |
| 12/09/2025 | COT - HCPL - Plumbing Final | N/A | Partial Pass | OK for Level Two TCO for all Levels. |
| 07/16/2024 | COT - FCON - Sprinkler - Final | N/A | Not Ready | customer did not understand inspection descriptions |
| 12/17/2025 | ENGR Engineering Final | N/A | Partial Pass | Okay for Level 4 TCO 12/17/25 Bollards need to be finished/painted per plan. Riprap needs to be placed on slope over 3:1 at NW corner Drainage Structure. WHIA basins At east side of parking lot need to be completed. Fence at West side is being installed now. All Construction Materials and Equipment will need to be secured inside temporary fencing At SW corner of parking lot adjacent to Basin. Not to go past Bullnoses of curbs. While using reach fork or other equipment during duration of TCO flaggers must assist operator to keep public safe from equipment. Okay for Level 4 TCO Schedule this inspection when ready to close out final. |
| 12/16/2025 | COT - HCBU - TCO | N/A | Partial Pass | OK for Level Three TCO for Levels 1 and 2. |
| 12/19/2025 | COT - HCBU - CofO | N/A | Partial Pass | 12/19/25: OK for Level Four TCO. |
| 11/24/2025 | COT - FCON - Fire - Final | N/A | Partial Pass | floors 2-3-4 passed. |
Completed Inspections
Permit Status: Issued
Permit Number: TC-COM-1023-02505
Permit Description: This for the construction of a new Group I-2 Institutional - Condition 2, Type I-B Construction, 4 Story In-Patient Rehabilitation Hospital at 355 N. Wilmot Road, Tucson. This will be for the Building Permit connected with the civil and rezoning of the site for Account No. TD-DEV-0623-00283 being currently reviewed.
Total Completed Inspections - 43