Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Underground
Permit Number - TC-COM-1023-02505
Inspection Description - COT - HCEL - Electrical Underground
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2024 | COT - HCEL - Electrical Underground | Partial Pass | 150’ of 2” conduit 36” depth for cox communication heading north side of property. 100’ of 4” conduit 36” depth for century link heading out east side of property. 10 parallel 4” conduit 5’ 10 depth for TEP switch boards west side of property. Okay to backfill progress areas. 6/21/2024 |
|
07/08/2024 | COT - HCEL - Electrical Underground | Partial Pass | Main duct bank distribution. Through wall to generator. Kitchen conduits. | |
07/15/2024 | COT - HCEL - Electrical Underground | Partial Pass | 10-3" conduits, and 4-2" conduits at electrical room. | |
07/26/2024 | COT - HCEL - Electrical Underground | Canceled | 7/26/24: canceled contractors not on site to request specific areas of work to be inspected | |
07/30/2024 | COT - HCEL - Electrical Underground | Not Ready | 7/30/24: needed ufer inspection | |
08/06/2024 | COT - HCEL - Electrical Underground | Canceled | No one on site knew what needs inspection, and work is covered. | |
08/08/2024 | COT - HCEL - Electrical Underground | Partial Pass | Electric Rooms. | |
09/10/2024 | COT - HCEL - Electrical Underground | Partial Pass | 9/10/24: from electrical room to kitchen area | |
09/24/2024 | COT - HCEL - Electrical Underground | Passed |