Parcel: 12714003C


Addresses:

355 N WILMOT RD


Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Underground 

Permit Number - TC-COM-1023-02505

Inspection Description - COT - HCEL - Electrical Underground 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
06/21/2024 COT - HCEL - Electrical Underground  Partial Pass 150’ of 2” conduit 36” depth for cox communication heading north side of property.
100’ of 4” conduit 36” depth for century link heading out east side of property.
10 parallel 4” conduit 5’ 10 depth for TEP switch boards west side of property. Okay to backfill progress areas. 6/21/2024
07/08/2024 COT - HCEL - Electrical Underground  Partial Pass Main duct bank distribution. Through wall to generator. Kitchen conduits.
07/15/2024 COT - HCEL - Electrical Underground  Partial Pass 10-3" conduits, and 4-2" conduits at electrical room.
07/26/2024 COT - HCEL - Electrical Underground  Canceled 7/26/24: canceled contractors not on site to request specific areas of work to be inspected
07/30/2024 COT - HCEL - Electrical Underground  Not Ready 7/30/24: needed ufer inspection
08/06/2024 COT - HCEL - Electrical Underground  Canceled No one on site knew what needs inspection, and work is covered.
08/08/2024 COT - HCEL - Electrical Underground  Partial Pass Electric Rooms.
09/10/2024 COT - HCEL - Electrical Underground  Partial Pass 9/10/24: from electrical room to kitchen area
09/24/2024 COT - HCEL - Electrical Underground  Passed