Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL OTHER
Apply Date:
05/09/2016
Applicant:
KENT WILLCOX
Description:
HOSPITAL
Architects:
  • PASSEY, CRAIG
Contractors:
  • HENSEL PHELPS CONSTRUCTION CO ,

Permit Reviews

Permit Number - T16CM03514
Permit Status: C of o
Permit Description: HOSPITAL
Start Date Submittal Complete Date Status  
02/09/2017 REVISION - - 2ND 03/06/2017 COMPLETED Review Details
03/06/2017 REVISION - - 6TH 03/16/2017 COMPLETED Review Details
05/09/2016 PLANS OK TO SUBMIT - COMM 05/09/2016 COMPLETED Review Details
05/09/2016 COMMERCIAL - NEW 06/09/2016 COMPLETED Review Details
06/23/2016 RESUBMITTAL 07/19/2016 COMPLETED Review Details
06/28/2018 REVISION - - 8TH 06/28/2018 COMPLETED Review Details
07/19/2016 RESUBMITTAL 07/28/2016 COMPLETED Review Details
07/28/2016 RESUBMITTAL 08/04/2016 COMPLETED Review Details
07/31/2017 REVISION - - 7TH 06/28/2018 COMPLETED Review Details
08/08/2016 REVISION - - 1ST 08/24/2016 COMPLETED Review Details
10/04/2016 REVISION - - 2ND 12/15/2016 COMPLETED Review Details
11/29/2016 REVISION - - 3RD 03/16/2017 COMPLETED Review Details
12/15/2016 REVISION - - 2ND 02/09/2017 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T16CM03514
Permit Status: C of o
Permit Description: HOSPITAL
Total Outstanding Activity Conditions - 1
Date Name
05/09/2016 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T16CM03514
Permit Description: HOSPITAL
Total Completed Inspections - 38
Date Description Inspector Results Comments
06/17/2016 ZONING - FINAL S SHIELDS Approved ZONING FINAL TO ENSURE THAT A HOLD IS PUT ON THE C OF O FOR THE BUILDING PLAN WHEN SUBMITTED, SEE L/H/N
12/11/2016 ELECTRIC - UNDERGROUND JBURGE Approved 4 ELECTRIC BOXES (FRAMED) - 2 AT GL: C/2.5 - 3; 2 AT GL: 2/D - E (FRAMED). CONDUITS:14 AT 2 1/2 INCHES; 8 AT 1".
12/14/2016 PLUMBING - ROUGH, SOIL JBURGE Approved 4" DOMESTIC WATER LINE AT GL: G.2/6.25 - 7.25. OK TO COVER PROGRESS AREA.
12/19/2016 BUILDING PRE-SLAB JBURGE Approved SLAB ON GRADE: AREA 6; GL: A/2 -4, 4/A - G, G/2 - 4, 2/A - G. OK TO PLACE CONCRETE WHEN REBAR IS IN PLACE - REMOVE WATER IN LOW LYING AREAS.
12/27/2016 BUILDING - PROGRESS JBURGE Approved COLUMNS AT GL: 11/C - F; (4): 12/D - E (3); 13/C - F (4); 14/C - D (2); SHEAR WALL AT 14/D. FORMS SET - OK TO PLACE CONCRETE.
12/30/2016 PLUMBING - INTERMEDIATE JBURGE Approved VAULT #1 - 2" WASTE LINE AT GL: C.5 - D.5/ 1.5 - 1.8; VAULT #2 2" WASTE LINE AT GL: A.3 - B.8/1.5 - 1.8; VAULT #3 - 2" WASTE LINE AT GL: A.3 - B.9/2.5 - 3.1
12/30/2016 PLUMBING - ROOF DRAINS JBURGE Approved ROOF DRAIN AT GL: 13/H (8" - 6" LINES)
05/16/2017 TEP CLEARANCE - AM JBURGE Approved ECO #10185 (2 METERS)
06/15/2017 PLUMBING - PROGRESS BSTEVENS Approved
07/10/2017 FIREWALL/FIREBARRIER/FIRESTOP JBURGE Approved FIRE CAULKING ON LEVEL #3, EAST AND WEST SHFTS. FIRST LAYER OF SHEETROCK.
08/14/2017 PLUMBING - ABOVE CEILING JBURGE Approved LEVEL #7, TOWER #4, HEATED HOT WATER LINES (1/2" - 2") TESTED AT 150 psi: SECTIONS #4, 5, 6.
08/14/2017 MECHANICAL - INTERMEDIATE JBURGE Approved
08/14/2017 PLUMBING - ABOVE CEILING JBURGE Approved WASTE AND VENT LINES (1 1/2" - 4") GL: D - F/ 10 - 12.
10/19/2017 GAS CLEARANCE JBURGE Approved
11/17/2017 FRAMING JBURGE Approved LINAC #4, CONTROL ROOM #1B217. OK TO SHEETROCK INTERIOR WALLS.
11/17/2017 SHEET ROCK NAILING JBURGE Approved LINAC #3, INTERIOR WALLS AND CEILING. OK TO TAPE PROGRESS AREAS.
11/22/2017 ENGINEERING - FINAL DROBERTS Approved OK FOR THE TEMPORARY USE OF PARTS OF THE PARKING LOT SOUTH OF THIS SITE FOR VALET PARKING ONLY, NO PUBLIC USE WITHIN THIS AREA ALLOWED.

WILL WORK WITH THE CONTRACTOR TO ENSURE THAT ALL OF THE SITE IS COMPLETE SO THAT THE DEVELOPMENT PACKAGE CAN BE FULLY APPROVED ON DECEMBER 6TH IF THEY COMPLETE ALL OF THE REQUIRED WOR FOR THIS AREA.
12/07/2017 ELECTRIC - INTERMEDIATE JBURGE Approved SPOT CHECKED GFCI OUTLETS ON LEVELS #1, 2, 3. NO PROBLEMS WERE FOUND.
12/13/2017 MECHANICAL - FINAL RSHERRY Approved REVIEW OF PRELIMINARY HVAC BALANCE REPORT COMPLETE
12/14/2017 PLUMBING - FINAL AQUIROZ Approved STERILIZATION COMPLETED FOR PHASE 1 AND SENT TO RECORDS
12/19/2017 FIRE - FINAL JPEELDAVIS Approved Need to correct the address issues pr COT BCO. Need contrasting colors, address numbers and building numbers. COT BCO to have the final say on this project. Also, this is only for phas 1 & 2.
12/21/2017 BUILDING - FINAL JBURGE Approved NEED ADDRESSING FOR BUILDINGS #1 AND #2.
10/02/2018 MECHANICAL - ABOVE CEILING JBURGE Approved PET CT Rooms #1A140, 1A141, 1A142, 1A142, 1A144, 1A145. OK to insulate progress areas.
04/11/2019 MECHANICAL - HYDRONIC PIPING JBURGE Approved
04/11/2019 OUTDOOR LIGHTING FINAL JBURGE Approved
04/11/2019 ELECTRIC - OUTDOOR LIGHTING JBURGE Approved
04/11/2019 ELECTRIC - PROGRESS JBURGE Approved
04/11/2019 ELECTRIC - CONSTRUCTION POWER JBURGE Approved
04/11/2019 ELECTRIC - TEMPORARY SERVICE JBURGE Approved
04/11/2019 ELECTRIC - ABOVE CEILING JBURGE Approved
04/11/2019 ELECTRIC - UFER JBURGE Approved
04/11/2019 ELECTRIC - FINAL JBURGE Approved
04/11/2019 PLUMBING - MEDICAL GAS/FINAL JBURGE Approved
04/11/2019 SITE - SEWER JBURGE Approved
04/11/2019 PLUMBING - BACK WATER VALVE JBURGE Approved
04/11/2019 PLUMBING - MEDICAL GAS/TEST JBURGE Approved
04/11/2019 PLUMBING - MD GAS/PRECONST MTG JBURGE Approved
04/11/2019 PLUMBING - YARD WTR LINE/TEST JBURGE Approved