Permit: T16CM03514

Parcel: 11202003D

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T16CM03514

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/11/2019 FIRE - FINAL Approved
12/19/2017 FIRE - FINAL Partial Approval Need to correct the address issues pr COT BCO. Need contrasting colors, address numbers and building numbers. COT BCO to have the final say on this project. Also, this is only for phas 1 & 2.
12/07/2017 FIRE - FINAL Partial Approval OK FOR TCO UNTIL DECEMBER 22ND 2017 FOR STAFF ONLY.

Need 1" red/white labels on all ceiling T grid to ID FSD
Need to fire caulk at FACP room and L2 east and west misc areas
Need to add duct work access hatch at double access door damper location L3
Need to add ductwork access hatch at 3H194
Need yo move duct detector north 2' at 3H183
Provide service contrract for fire sprinkler, fire alarm, generator and dampers
FACP sign to be red and white reflective
Unlatch gate in stair on alarm
Breaker locks for the fire alarm