Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T16CM03514
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2019 | FIRE - FINAL | Approved | ||
| 12/19/2017 | FIRE - FINAL | Partial Approval | Need to correct the address issues pr COT BCO. Need contrasting colors, address numbers and building numbers. COT BCO to have the final say on this project. Also, this is only for phas 1 & 2. | |
| 12/07/2017 | FIRE - FINAL | Partial Approval | OK FOR TCO UNTIL DECEMBER 22ND 2017 FOR STAFF ONLY. Need 1" red/white labels on all ceiling T grid to ID FSD Need to fire caulk at FACP room and L2 east and west misc areas Need to add duct work access hatch at double access door damper location L3 Need to add ductwork access hatch at 3H194 Need yo move duct detector north 2' at 3H183 Provide service contrract for fire sprinkler, fire alarm, generator and dampers FACP sign to be red and white reflective Unlatch gate in stair on alarm Breaker locks for the fire alarm |