Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T16CM03514

Parcel: 11202003D

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/11/2019 PLUMBING - ROUGH, SOIL Approved
06/23/2017 PLUMBING - ROUGH, SOIL Not ready for Inspection
06/23/2017 PLUMBING - ROUGH, SOIL Partial Approval CHILLED WATER LINE (12" PRIMARY LINE) AT GL: 14/I - K TESTED AT 164 psi. OK TO COVER PROGRESS AREA.
01/05/2017 PLUMBING - ROUGH, SOIL Partial Approval 4" DOMESTIC WATER LINE AT GL: H/9; UNDER TEST AT 100 PSI - OK TO COVER.
12/14/2016 PLUMBING - ROUGH, SOIL Partial Approval 4" DOMESTIC WATER LINE AT GL: G.2/6.25 - 7.25. OK TO COVER PROGRESS AREA.
12/06/2016 PLUMBING - ROUGH, SOIL Partial Approval 3" LINE AT GL: C.6/ 1.5 - 1.8 (2" T's RUNNING NORTH AND SOUTH AT GL: 1.75/ C - C.6) OK TO COVER PROGRESS AEAS.
11/03/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection
10/31/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection
10/30/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection
10/25/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection
10/19/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection
10/19/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection
10/17/2016 PLUMBING - ROUGH, SOIL Partial Approval STORM DRAIN TIE-IN (6" TO 8") AT GL: 9.1/ B.8 - C. OK TO COVER PROGRESS AREA.
10/10/2016 PLUMBING - ROUGH, SOIL Partial Approval 4" WASTE LINES AT GL: D/4 - D/3; 2" LINES AT D.3 - D/ 3.2; D/3 - 2 (3"); D.75/ 3 - 2 (4" - 2"); VENTS AT GL: D.75/2.25 (2" - 2 1/2") C.75 - D/ 2.75 4" LINE; 3.25/C - D 4" LINE; C.5/3 -2 4" WASTE LINE. OK
10/07/2016 PLUMBING - ROUGH, SOIL Partial Approval 6" SANITARY SEWER DRAIN CLEAN OUT AT GL: B.8 - C/6.5
10/06/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection
10/04/2016 PLUMBING - ROUGH, SOIL Partial Approval 6" SANITARY SEWER DRAIN AT GL: B.8 - C/6.5. OK TO COVER PROGRESS AREA.
10/03/2016 PLUMBING - ROUGH, SOIL Partial Approval 8" STORM DRAINS AT GL: H/10.5; B - C/6 - 7.5. OK TO COVER PROGRESS AREAS.
10/03/2016 PLUMBING - ROUGH, SOIL Partial Approval STORM DRAIN (8") AT GL: H/9.5; STORM DRAI (8") AT GL: H/13.5; SEWER LINE (8") AT GL: C - C.8/12.5 - 13. OK TO COVER PROGRESS AREAS.
09/30/2016 PLUMBING - ROUGH, SOIL Partial Approval 8" STORM DRAIN DIE-IN AT GL: C/6.5; 4" - 2 1/2" WASTE AND VENT LINES AT GL: D.5 - E/ 4 - 5, D - F/4 - 4.5; 4 - 3.75/E - F.5; E/3.75 - 2.5. OK TO COVER PROGRESS AREAS.
09/26/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection
09/26/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection
09/22/2016 PLUMBING - ROUGH, SOIL Partial Approval WASTE AND VENT LINES AT GL: 8/C.25 (8"), C - F.25/ 6.5 (6"); D/6 (2 1/2"), E/6 - 5 (6"); D.5/ 6 - 5 (6"); E.5 - F/6.5 - 7 (4" - 2 1/2"); D.25 - F/ 5.5 - 6 (4"); E/5 - 6 (3"); 6/D.75 - E (4"); D.25/ 5.5 - 4.25 (4"); 5.25/C.75 - D.25 (3"). OK TO COVER PRGRESS AREAS.
09/19/2016 PLUMBING - ROUGH, SOIL Partial Approval 8" STORM DRAINS AT GL: C - D.25/7.5; D.25 - 6.25. OK TO COVER PROGRESS AREAS.
09/15/2016 PLUMBING - ROUGH, SOIL Partial Approval 4" - 3" - 2.5" WASTE AND VENT LINES AT GL: 9.5 - 11.5/ G- G.8; E - G.5/ 10.5 - 9. OK TO COVER PROGRESS AREAS.
09/15/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection INFORMATION ONLY.
09/13/2016 PLUMBING - ROUGH, SOIL Partial Approval 4" WATER LINE AT GL: G/9 TESTED AT 130 psi; 4" STORM DRAIN AT GL: H/9; 2" WASTE LINES AT GL: E.25 - E.75/ 7 - 8; E.75 - F/ 7.5 - 8; 4" WASTE LINE AT GL: E.5/ 7 - 7.8. OK TO COVER PROGRESS AREAS.
09/09/2016 PLUMBING - ROUGH, SOIL Partial Approval WASTE LINES AND VENTS AT GL: F.8 - H/10 - 11. OK TO COVER PROGRESS AREAS.
09/07/2016 PLUMBING - ROUGH, SOIL Cancelled
09/06/2016 PLUMBING - ROUGH, SOIL Partial Approval WASTE (7.8 TO 8.5 / C.2 TO D) AND (8.4 TO 10.2 / C.2 TO D)
GREASE LINE (8.4 TO 10.2 / C.2) ALL TESTED AND OK TO COVER.
09/01/2016 PLUMBING - ROUGH, SOIL Partial Approval SECTION B-2; WASTE LINES AND RISERS AT GL: 9 - 8/D.9 - E.5. OK TO COVER PROGRESS AREAS.
08/30/2016 PLUMBING - ROUGH, SOIL Partial Approval 8" STORM DRAIN AT GL: G.3/10.5. OK TO COVER PROGRRESS AREA.
08/26/2016 PLUMBING - ROUGH, SOIL Partial Approval 2" - 6" WASTE LINES AND RISERS AT GL: D - G.8/ 11 - 14. OK TO COVER PROGRESS AREAS.
08/25/2016 PLUMBING - ROUGH, SOIL Partial Approval 8" STORM DRAIN AT GL: G.5/13.5. OK TO COVER PROGRESS AREA.
08/22/2016 PLUMBING - ROUGH, SOIL Not ready for Inspection NOT READY
08/19/2016 PLUMBING - ROUGH, SOIL Partial Approval WASTE AND VENT LINES AT 2.5" - 6" LINES. GL: D.5 - H/14 - 17. OK TO COVER PROGRESS AREAS.
08/12/2016 PLUMBING - ROUGH, SOIL Partial Approval 2 1/2 " LINE AT GL: 19-F - H; OK TO COVER PROGRESS AREA.
08/08/2016 PLUMBING - ROUGH, SOIL Partial Approval WASTE AND VENT LINES; 8" ROOF DRAIN AT 4' WESTOF COLUMN 17' 5' FROM COLUMN LINE #20; F.5 - H. OK TO COVER PROGRESS AREAS.
08/05/2016 PLUMBING - ROUGH, SOIL Partial Approval 4" WASTE LINE AT GL: 17/E - F, 8" ROOF DRAIN AT E/19 - 20; CLEAN OUTS AND VENT LINES AI AREA OF E/19 - 20.