Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T16CM03514
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2019 | ELECTRIC - INTERMEDIATE | Approved | ||
| 09/26/2018 | ELECTRIC - INTERMEDIATE | Partial Approval | MRI-3T, Rooms # 1A117, 1A118. Ok to cover walls | |
| 09/21/2018 | ELECTRIC - INTERMEDIATE | Partial Approval | PET-CT ROOMS #140 through #145. | |
| 01/10/2018 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | FRAMING STUD NEEDS TO BE MOVED (HCR #3) AWAY FROM ELECTRIC CONDUIT TO ALLOW FOR PROPER INSTALLATION OF SHEETROCK. | |
| 12/07/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | SPOT CHECKED GFCI OUTLETS ON LEVELS #1, 2, 3. NO PROBLEMS WERE FOUND. | |
| 12/06/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | OVER HEAD LIGHTING IN LINAX #1 AND LINAX #2. | |
| 11/17/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | LINAC #3, CONTROL ROOM #AB217 - ELECTRIC IN WALLS. OK TO COVER WALLS. | |
| 11/13/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRIC IN WALLS IN LINAC #3, OK TO COVER WALLS. | |
| 11/06/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | LINAC #2, LINAC CORRIDOR, CONTROL ROOMS #1B237, 1B232; CAMERA ROOMS #1A136, 1A137 (SOUTH AND WEST WALLS); IN WALL ELECTRICITY. | |
| 10/26/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | IN WALL ELECTRIC AT LINAC #1. OK TO COVER WALLS. | |
| 10/10/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | E;ECTRIC PANELS: LEVEL #1: LPW1A, 1B, 1C; LEVEL #2: LPE2A, 2B, 2C; LEVEL #3 LPE3C. OK TO ENERGIZE PANELS. | |
| 09/26/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRIC PANELS #HMP-1, HMP-2, HMP-3, LE -3. OK TO ENERGIZE PANCELS. | |
| 09/25/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRIC PANELS #LMW1, LMW2, LMW3. OK TO ENERGIZED PANELS. | |
| 09/22/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 09/05/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL #1, PANEL #LME-1; LEVEL #2, PANEL #2, LME-2. OK TO ENERGIZE PANEL LME-1. LEM-2 TO BE ENERGIZED AT A LATER DATE. | |
| 08/25/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 08/24/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL #2, PANEL HLE -2; OK TO ENERGIZE PANEL FRO LEVELS #1 & 2; LOCK OUT, TAG OUT MUST BE USED IN THIS PANEL. | |
| 08/22/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | LIGHT POLE CAISSONS: ALLEN ROAD (4), PARKING STRUCTURE (2). OK TO PLACE CONCRETE. | |
| 08/21/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 08/17/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | UTILITY PLANT, ELECTRIC PANEL #PCP- MSD-1 AT 1200 AMPS. OK TO ENERGIZE. | |
| 08/16/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL #3, ELECTRIC IN WALLS: GL: C - H/7 - 12. OK TO COVER WALLS. | |
| 08/11/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
| 08/11/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 08/07/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 08/03/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 08/02/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 08/01/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/31/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRIC IN WALLS AT GL: D - H/12 - 14.5 ON LEVEL #3. | |
| 07/26/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/25/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/24/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/21/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/20/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRIC ROOM #1A218: PANELS: LME-1, HLE-1, LPE-1B, LPE-1A, GDPPE. OK TO ENERGIZE PANELS. | |
| 07/18/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | AREAS 11 - 14; GL: 5 - 9/C - G: ELECTRIC IN WALLS, OK TO ON SIDE SHEET ROCK. | |
| 07/17/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/14/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRIC UNDERGROUND - SIX CAISSON LIGHT POLE FOOTINGS WITH 3/4" CCONDUIT LINES. | |
| 07/13/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/12/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/12/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/11/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/10/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 07/07/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | POLE LIGHT CAISSONS; 6 @ PARKING SRUCTURE; 3 @ ALLEN CENTER. OK TO POUR CAISSON FOOTINGS. | |
| 07/05/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 06/29/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 06/23/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 06/22/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRIC IN WALLS IN ROOMS AT GL: D - G/8 - 10 | |
| 06/20/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 06/19/2017 | ELECTRIC - INTERMEDIATE | Cancelled | WORK INCOMPLETE. | |
| 06/16/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 06/15/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL 3 ELEVATOR 1,2,3,4 CONTROL PANELS OK. | |
| 06/14/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 06/13/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE. | |
| 06/12/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL #2: GL: D - H/10 - 12. OK TO COVER WALLS. | |
| 06/09/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | UNDERGROUND CONDUITS AT NORTH OF TRASH ENCLOSURE: 2 @ 3/4" CONDUITS. OK TO COVER PROGRESS AREA. | |
| 06/08/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | DISCONNECTS FOR AIR HANDLERS #1 & #2. | |
| 06/07/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE | |
| 06/06/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE | |
| 06/02/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | PARTIAL. INFORMATION. ROOD LEVEL: LOCATION OF FEEDER LINES TO AIR HANDLERS # 1 & #2. | |
| 06/01/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | RESCHEDULED FOR 2 JUNE | |
| 05/31/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | EMERGENCY GENERATOR; TRANSFER SWITCHES: DP-HELV; APS-ELV ON LEVEL #1. LEVEL #2, PANEL MDPE3. | |
| 05/30/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE | |
| 05/29/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE | |
| 05/25/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE | |
| 05/24/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE. | |
| 05/23/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | LEVEL #2, ROOMS IN AREA AT GL: E - H/12 - 15. | |
| 05/22/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE. | |
| 05/19/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE. | |
| 05/18/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE | |
| 05/17/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE | |
| 05/16/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | WORK INCOMPLETE | |
| 05/15/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRIC ROOM #10185, SES UNITS #1 AND #2; MSB #1 AND MSB #2. OK TO ENERGISE UNITS. | |
| 05/12/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | AREAS #1 - 4, LEVEL #2; GL: C - G/15 - 19 | |
| 05/11/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | BOXES AND SWITCHES IN ROOMS AT GL: C - G/4 - 7. OK TO INSULATE AND COVER WALLS. | |
| 05/10/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | ||
| 05/09/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | ||
| 05/08/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | X-FORMER IN GARAGE FIRST FLOOR OK TO CLOSE. | |
| 05/05/2017 | ELECTRIC - INTERMEDIATE | Cancelled | ||
| 05/04/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | ||
| 05/03/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | ||
| 05/02/2017 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | NOT READY | |
| 04/28/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | AREAS 3, 4, 5, 6. | |
| 04/21/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | IFORMATION ONLY: RE: ADDITIONAL LUGS FOR SES CABINET. | |
| 03/14/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | PRELIMINARY WALK THROUGH: SWITHCH BOXES, OUTLET BOXES, FIRER ALARM BOXES, DATA BOXES, LOW VOLTAGE BOXES IN AREAS AT GL: F/8 - 20; D - H/8 - 20. ALL AREAS TO BE RECHECKED WHEN NEEDED MATERIALS ARRIVE. | |
| 01/19/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | 4" CONDUITS INTO EACH VAULT (4 CONDUITS PER VAULT, 4 VAULTS |