Permit: T07CM04561
Permit Details
Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
10410 E RITA RANCH RD #100
Address NEW:
10410 E RITA RANCH RD #100
Apply Date:
12/06/2007
Applicant:
N/A
Description:
DENTAL OFFICE
Contractors:
- COUES RIDGE CONSTRUCTION L L C
Permit Reviews
Permit Number - T07CM04561
Permit Status: C of o
Permit Description: DENTAL OFFICE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/16/2009 | REVISION - - 2ND | 01/16/2009 | COMPLETED |
| 02/11/2008 | 3RD PARTY REVIEW-COMMERCIAL TI | 02/11/2008 | COMPLETED |
| 02/11/2008 | POST 3RD PARTY REVIEW | 02/20/2008 | COMPLETED |
| 07/28/2008 | REVISION - - 1ST | 07/28/2008 | COMPLETED |
| 12/06/2007 | COMMERCIAL TI | 02/11/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07CM04561
Permit Status: C of o
Permit Description: DENTAL OFFICE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/06/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T07CM04561
Permit Description: DENTAL OFFICE
Total Completed Inspections - 35
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2008 | PLUMBING - ROUGH, SOIL | RRICH | Approved | IVRS - Inspection :* PIPE WRAPS OK NOTE: SEE YOUR NOTES ON PAGE P.3 #12 & #13 YOU NEED TO HAVE A MEDICAL GAS PRE-CON MEETING WITH YOUR 3RD PARTY AND C.O.T INSPECTOR PER PLAN. I HAVE ADDED 03043 MEDICAL GAS PRE-CONSTRUCTION MEETING, 03045 MEDICAL GAS PRESSURE TEST, 03089 MEDICAL GAS FINAL TO YOUR PERMIT CARD 3RD PARTY INSPECTION IS REQUIRED ON YOUR SYSTEM OBTAIN THAT INSPECTOR CALL IN 03043 AND CALL ME AT 240-0248 TO SCHEDULE THIS MEETING, WITH YOUR CERTIFIED INSTALLER, YOURSELF, 3RD PARTY INSPECTOR AND ME. PRIOR TO CONTINUE AIR & VACUUM WORK. YOU HAVE COVERED AGAIN WITHOUT INSPECTION. |
| 06/09/2008 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection :* DWV WATER TEST THRU ROOF OK WATER DISTRIBUTION OK |
| 06/09/2008 | PLUMBING - MEDICAL GAS/FINAL | RRICH | Approved | IVRS - Inspection :* |
| 06/09/2008 | PLUMBING - MEDICAL GAS/TEST | RRICH | Approved | IVRS - Inspection :* |
| 06/09/2008 | PLUMBING - MD GAS/PRECONST MTG | RRICH | Approved | IVRS - Inspection :* |
| 07/15/2008 | PLUMBING - ABOVE CEILING | RRICH | Approved | IVRS - Inspection :* RECEIVED LETTER DELETING MEDICAL GAS REQUIREMENTS, AND DELETING HOT & HOT RETURN TO SINKS IN ROOMS 109, 110, 113, 114, 115, 116, 117, 118 (OPERATORY 1-7 & CONSULTATION ROOM) |
| 08/04/2008 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* THE PRIMARY & SECONDARY DRAINS ARE SWITCHED PRIMARY IS CONNECTED TO SECONDARY DRAIN PAN WILL CHECK ON FINAL OK FOR SHEETROCK |
| 08/19/2008 | REINFORCED MASONRY PRE-GROUT | GDABBS | Approved | IVRS - Inspection :* |
| 10/03/2008 | SHEET ROCK NAILING | GDABBS | Approved | IVRS - Inspection :* |
| 10/03/2008 | U VALUE FOR WINDOW | GDABBS | Approved | IVRS - Inspection :* |
| 10/03/2008 | BUILDING ABOVE CEILING | GDABBS | Approved | IVRS - Inspection :* |
| 10/03/2008 | FRAMING | GDABBS | Approved | IVRS - Inspection :* |
| 12/09/2008 | BUILDING - PROGRESS | GDABBS | Approved | IVRS - Inspection :* |
| 12/12/2008 | ELECTRIC - ABOVE CEILING | RJIROUDE | Approved | IVRS - Inspection :* |
| 12/12/2008 | ELECTRIC - INTERMEDIATE | RJIROUDE | Approved | IVRS - Inspection :* |
| 12/12/2008 | ELECTRIC - UNDERGROUND | RJIROUDE | Approved | IVRS - Inspection :* |
| 12/18/2008 | ELECTRIC - PROGRESS | RJIROUDE | Approved | IVRS - Inspection :* 1) SERVICE INSPECTION |
| 12/19/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED FOR #100 PER R. JIROUDEK |
| 12/23/2008 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE ACCESS TO ROOFTOP EQUIPMENT AND FAN COIL IN ATTIC. PROVIDE AIR BALANCE REPORT. RELOCATE CONDENSOR MIN. 12" FROM WALL, 24" ON SERVICE SIDE. |
| 12/23/2008 | MECHANICAL - PROGRESS | JMILITEL | Approved | IVRS - Inspection :* |
| 12/23/2008 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
| 01/13/2009 | RIGHT OF WAY - FINAL | MCASTRO | Approved | PER EMAIL |
| 01/13/2009 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 01/13/2009 | NPPO - FINAL | ACONNOR | Approved | N/A |
| 01/13/2009 | LANDSCAPE - FINAL | ACONNOR | Approved | N/A |
| 01/14/2009 | PLUMBING - PROGRESS | RRICH | Approved | IVRS - Inspection :* |
| 01/20/2009 | OUTDOOR LIGHTING FINAL | RJIROUDE | Approved | IVRS - Inspection :* |
| 01/20/2009 | ELECTRIC - FINAL | RJIROUDE | Approved | IVRS - Inspection :* |
| 01/20/2009 | ELECTRIC - OUTDOOR LIGHTING | RJIROUDE | Approved | IVRS - Inspection :* |
| 01/21/2009 | FIRE - FINAL | LTHOMAS | Approved | |
| 01/22/2009 | SITE - SEWER | RRICH | Approved | IVRS - Inspection :* |
| 01/26/2009 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* RECEIVED IN HOUSE BACKFLOW CERTIFICATIONS & CHLORINE & BACTERIA REPORT FOR POTABLE WATER SYSTEM. RECEIVED LETTER FOR FUTURE SINKS AT ROOMS 115, 116, 117 AND 118 |
| 01/26/2009 | BUILDING - FINAL | GDABBS | Approved | IVRS - Inspection :* |
| 01/27/2009 | ENGINEERING - FINAL | NKALAHAR | Approved | OUTSTANDING ISSUES TO BE HELD TO GRADING PERMIT T07BU02193 |
| 01/30/2009 | PERMIT FINALED | LJACKSON | Approved |