Permit: T07CM04561

Parcel: 14117015B

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/04/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
THE PRIMARY & SECONDARY DRAINS ARE SWITCHED
PRIMARY IS CONNECTED TO SECONDARY DRAIN PAN
WILL CHECK ON FINAL
OK FOR SHEETROCK
08/01/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
USE PRIMER ON ALL PVC FITTINGS
SUPPORT WITH HANGER STRAP
DRAIN PAN MUST BE MIN. 1 1/2" LARGER THAN FAN COIL
07/30/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. USE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
2. SUPPORT PVC CONDENSATE DRAIN EVERY 4'
3. DO NOT ATTACH SUPPORTS TO ELEC. CONDUITS
4. RELOCATE CONDENSATE DRAINS BLOCKING ACCESS OPENING IN CEILING.
5. DRAIN PAN MUST FIT ENTIRELY UNDER FAN COIL 1 1/2" ON ALL SIDES
6. PROVIDE BACKING AROUND CEILING BOXES AND
SIDEWALK BOXES
7. RECALL FOR INSPECTION
07/15/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR SHEETROCK NORTH PART OF BLDG.
REMOVE SCREEN FROM DRYER VENT
PROVIDE A CONDENSATE DRAIN
PROVIDE PERMANENT ACCESS IN & OUT OF ROOF WELL