Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* THE PRIMARY & SECONDARY DRAINS ARE SWITCHED PRIMARY IS CONNECTED TO SECONDARY DRAIN PAN WILL CHECK ON FINAL OK FOR SHEETROCK |
|
| 08/01/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* USE PRIMER ON ALL PVC FITTINGS SUPPORT WITH HANGER STRAP DRAIN PAN MUST BE MIN. 1 1/2" LARGER THAN FAN COIL |
|
| 07/30/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. USE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 2. SUPPORT PVC CONDENSATE DRAIN EVERY 4' 3. DO NOT ATTACH SUPPORTS TO ELEC. CONDUITS 4. RELOCATE CONDENSATE DRAINS BLOCKING ACCESS OPENING IN CEILING. 5. DRAIN PAN MUST FIT ENTIRELY UNDER FAN COIL 1 1/2" ON ALL SIDES 6. PROVIDE BACKING AROUND CEILING BOXES AND SIDEWALK BOXES 7. RECALL FOR INSPECTION |
|
| 07/15/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR SHEETROCK NORTH PART OF BLDG. REMOVE SCREEN FROM DRYER VENT PROVIDE A CONDENSATE DRAIN PROVIDE PERMANENT ACCESS IN & OUT OF ROOF WELL |