Permit: T07CM04561

Parcel: 14117015B

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
01/20/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
01/20/2009 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
01/14/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
MEETING TO DISCUSS CORRECTIONS
01/12/2009 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/09/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
12/18/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) SERVICE INSPECTION
12/17/2008 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
1. SERVICE CONDUCTORS CANNOT BE IN SAME RACEWAY AS NON-SERVICE CONDUCTORS
2. INSTALL MAIN BONDING JUMPER IN SERVICE DISCONNECT
3. MARK "SERVICE DISCONNECT"
12/10/2008 ELECTRIC - PROGRESS Denied IVRS - Inspection :
There is no access to the site.| 920*
BUILDING LOCKED
NO ACCESS
NO ONE ON SITE