Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/10/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* BUILDING LOCKED NO ACCESS NO ONE ON SITE |
|
| 09/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & CEILINGS @ ENTRY |
|
| 07/01/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. TIGHTEN LOOSE FITTINGS. THEN OK WALLS. 2. OK CEILINGS EXCEPT KITCHEN AND IT ROOMS |
|
| 06/13/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. RACEWAYS TO BE CONTINOUS IN WALLS OR ACCESSIBLE 2. PROTECT PVC CONDUIT AT STUDS & SUPPORT 3. SUPPORT VDV CABLING IN WALLS 725.24, 800.24 4. CANNOT USE FLEX CONDUIT IN AREAS FOR 517.13 CITY AMENDMENT FOR FLEX 5. SUPPORT CONDUITS WITHIN 3' OF BOXES 6. PLANS CALL FOR EMT IN WALLS IN GENERAL |