Permit: T07CM04561

Parcel: 14117015B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/12/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/10/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
BUILDING LOCKED
NO ACCESS
NO ONE ON SITE
09/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & CEILINGS @ ENTRY
07/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. TIGHTEN LOOSE FITTINGS. THEN OK WALLS.
2. OK CEILINGS EXCEPT KITCHEN AND IT ROOMS
06/13/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. RACEWAYS TO BE CONTINOUS IN WALLS OR ACCESSIBLE
2. PROTECT PVC CONDUIT AT STUDS & SUPPORT
3. SUPPORT VDV CABLING IN WALLS 725.24, 800.24
4. CANNOT USE FLEX CONDUIT IN AREAS FOR 517.13 CITY AMENDMENT FOR FLEX
5. SUPPORT CONDUITS WITHIN 3' OF BOXES
6. PLANS CALL FOR EMT IN WALLS IN GENERAL