Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED IN HOUSE BACKFLOW CERTIFICATIONS & CHLORINE & BACTERIA REPORT FOR POTABLE WATER SYSTEM. RECEIVED LETTER FOR FUTURE SINKS AT ROOMS 115, 116, 117 AND 118 |
|
| 01/21/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE WATER TIGHT FIXTURES 2. PROVIDE BACTERIA & CHLORINE REPORT FOR POTABLE WATER |
|
| 01/20/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 01/14/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ALL ITEMS FROM 1/13/08 INSPECTION |
|
| 01/13/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* EXPOSE LANDSCAPING TIE IN WATER SUPPLY COMPLETE INTERIOR FOUNTAIN FOR PROOF OF WATER SUPPLY OR EXPOSE WATER SUPPLY OR PERM CAP OF COMPLETE ALL SINK INSTALLS WITH EYEWASH 1. MAKE ALL FIXTURES WATER TIGHT 2. ALL CLEANOUTS WITH COVERS REQUIRE FACTORY TAPPED C/O PLUGS WITH MACHINE SCREWS 3. COMPLETE INSULATION ON HOT & RETURN PIPING 4. PROVIDE WATER HAMMER ARRESTORS FOR LAUNDRY BOX 5. PROVIDE CHLORINE & BACTERIA REPORT FOR POTABLE WATER SYSTEM 6. PROVIDE CERTIFICATIONS FOR ALL IN HOUSE BACKFLOW DEVICES 7. TERMINATE CLEANOUTS PROPERLY 8. PROPERLY PERM CAP ALL FUTURES PROVIDE A LETTER FOR FUTURES IN ROOMS 115, 116, 117, 118 SINKS STAMPED & SEALED BY ENGINEER 9. PERM CAP WATER FOR FUTURE T.I. SUPPLY |