Permit: T07CM04561

Parcel: 14117015B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/26/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED IN HOUSE BACKFLOW CERTIFICATIONS &
CHLORINE & BACTERIA REPORT FOR POTABLE WATER SYSTEM.
RECEIVED LETTER FOR FUTURE SINKS AT ROOMS 115, 116, 117 AND 118
01/21/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE WATER TIGHT FIXTURES
2. PROVIDE BACTERIA & CHLORINE REPORT FOR
POTABLE WATER
01/20/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
01/14/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ALL ITEMS FROM 1/13/08 INSPECTION
01/13/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
EXPOSE LANDSCAPING TIE IN WATER SUPPLY
COMPLETE INTERIOR FOUNTAIN FOR PROOF OF WATER SUPPLY OR EXPOSE WATER SUPPLY OR PERM CAP OF
COMPLETE ALL SINK INSTALLS WITH EYEWASH

1. MAKE ALL FIXTURES WATER TIGHT
2. ALL CLEANOUTS WITH COVERS REQUIRE FACTORY TAPPED C/O PLUGS WITH MACHINE SCREWS
3. COMPLETE INSULATION ON HOT & RETURN PIPING
4. PROVIDE WATER HAMMER ARRESTORS FOR LAUNDRY BOX
5. PROVIDE CHLORINE & BACTERIA REPORT FOR POTABLE WATER SYSTEM
6. PROVIDE CERTIFICATIONS FOR ALL IN HOUSE BACKFLOW DEVICES
7. TERMINATE CLEANOUTS PROPERLY
8. PROPERLY PERM CAP ALL FUTURES
PROVIDE A LETTER FOR FUTURES IN ROOMS 115, 116, 117, 118 SINKS STAMPED & SEALED BY ENGINEER
9. PERM CAP WATER FOR FUTURE T.I. SUPPLY