Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/01/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FLEX DUCTS STILL DON'T MEET THE REQUIREMENTS THE ENGINEER SET FORTH IN HIS LETTER. DUCTS WERE NOT SIZED PROPERLY AND HIGH EFFICIENCY TAKE OFFS WERE NOT USED. GET THE ENGINEER OK TO KEEP THE SYSTEMS THE WAY THEY ARE NOW. ON EXISTING UNITS BE SURE CONDENSATE IS TERMINATED TO AN APPROVED LOCATION. |
|
| 06/13/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* MECHANICAL SYSTEMS NOT INSTALLED PER DETAILS ON PLANS. HANGER STRAPS, FLEX DUCT CONNECTIONS, MAIN TRUNK LINES, CONDENSATE PIPING, SECONDARY DRAINS. USE ONLY UL LISTED TAPE ON FLEX DUCTS |