Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/14/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/13/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE FRESH AIR INTAKES ON ROOFTOP AC UNITS 2. LOW VOLTAGE WIRING OUTDOORS MUST BE PROTECTED 3. PROVIDE ISOLATION PADS UNDER CONDENSOR 4. PROVIDE BUSHINGS IN FAN COIL KNOCKOUTS FOR REFER LINES 5. EXTEND VENT ON CONDENSATE DRAIN ABOVE OUTLET ON FAN COIL 6. SUPPORT DRAIN LINE 7. PROVIDE AIR BALANCE REPORT |
|
| 12/23/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE ACCESS TO ROOFTOP EQUIPMENT AND FAN COIL IN ATTIC. PROVIDE AIR BALANCE REPORT. RELOCATE CONDENSOR MIN. 12" FROM WALL, 24" ON SERVICE SIDE. |