Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
4500 N ORACLE RD
Address NEW:
4500 N ORACLE RD
Apply Date:
08/30/2007
Applicant:
METRO PERMIT EXPRESS, INC *C
Description:
REMODEL: MACY'S AREA
Contractors:
  • LEDCOR CONSTRUCTION INC

Permit Reviews

Permit Number - T07CM03581
Permit Status: C of o
Permit Description: REMODEL: MACY'S AREA
Start Date Submittal Complete Date Status  
01/15/2008 RESUBMITTAL 01/25/2008 COMPLETED Review Details
02/05/2010 REVISION - - 3RD 02/08/2010 COMPLETED Review Details
03/05/2010 REVISION - - 4TH 03/05/2010 COMPLETED Review Details
04/04/2008 3RD PARTY REVIEW-REVISION/OTHER 04/29/2008 COMPLETED Review Details
04/21/2010 REVISION - - 5TH 04/26/2010 COMPLETED Review Details
04/28/2010 REVISION - - 6TH 05/06/2010 COMPLETED Review Details
05/06/2010 REVISION - - 6TH 05/06/2010 COMPLETED Review Details
06/04/2008 3RD PARTY REVIEW-REVISION/OTHER 06/10/2008 COMPLETED Review Details
06/16/2009 REVISION - - 1ST 06/22/2009 COMPLETED Review Details
06/22/2009 REVISION - - 1ST 07/21/2009 COMPLETED Review Details
07/21/2009 REVISION - - 1ST 07/29/2009 COMPLETED Review Details
08/07/2008 3RD PARTY REVIEW-REVISION/OTHER 08/11/2008 COMPLETED Review Details
08/22/2008 3RD PARTY REVIEW-REVISION/OTHER 10/24/2008 COMPLETED Review Details
08/30/2007 PLANS OK TO SUBMIT - COMM 09/17/2007 COMPLETED Review Details
09/11/2009 REVISION - - 2ND 09/18/2009 COMPLETED Review Details
09/17/2007 3RD PARTY REVIEW-COMMERCIAL TI 12/18/2007 COMPLETED Review Details
09/18/2009 REVISION - - 2ND 09/21/2009 COMPLETED Review Details
12/18/2007 POST 3RD PARTY REVIEW 01/15/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07CM03581
Permit Status: C of o
Permit Description: REMODEL: MACY'S AREA
Total Outstanding Activity Conditions - 1
Date Name
08/30/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T07CM03581
Permit Description: REMODEL: MACY'S AREA
Total Completed Inspections - 40
Date Description Inspector Results Comments
07/17/2008 EXT METAL CLIPS/EXT SHEATHING LHANLY Approved DENSGLASS
R5 LINE
U8 LINE
AND 8 LINE
09/18/2008 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*
ROOF DRAINS NOT INSTALLED PER PLAN
NO REDLINES ON SITE
11/04/2008 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
1. FOREVER 21 MED. PRESS AND EXH. COMPLETE
FIRE DAMPERS COMPLETE
2. VICTORIA's SECRET MED. PRESS & EXH. COMPLETE
FIRE DAMPERS COMPLETE
11/06/2008 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
6" STORM DRAIN AT BLDG "B"
11/07/2008 ELECTRIC - UNDERGROUND RHOLLAND Approved IVRS - Inspection :*
OK 3 - 4" STRUCTURE OUT & ACROSS ROAD
OK 4 - PVC TO STRUCTURE

1. BRACE/LASH CALBES SERVICE AND PULL BOX PER
MANUFACTURES INSTRUCTIONS
2. DO NOT ENERGIZE UNTIL AFTER CONCRETE IS POURED DUE TO SAFETY CONCERNS
11/19/2008 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
OK TO RELEASE POWER
11/19/2008 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
SERVICE
1. SEAL BOTTOM OF SWITCH GEARS
2. NEED PERMANENT LABELING

OK LASHINGS AT SERVICE AND PULL CABINET

ROOF:
1. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING
11/19/2008 TEP CLEARANCE - PM JWEATHER Approved TEC CLEARED PER L. HANLY
11/24/2008 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
1. NEED ARC FLASH LABELS
2. BOND GUTTER ENCLOSURES
3. TIGHTEN BUSHING
4. FINISH SUNGLASS HUT
5. FINISH #1 & #2 PREVIOUS
10/09/2009 ELECTRIC - OUTDOOR LIGHTING RHOLLAND Approved IVRS - Inspection :*
10/15/2009 NPPO - FINAL JLINVILLE Approved
10/15/2009 LANDSCAPE - FINAL JLINVILLE Approved
10/21/2009 REINFORCED MASONRY PRE-GROUT AQUIROZ Approved IVRS - Inspection :*
1) 2ND LIFT BLDG E, TOP OUT AT LOADING DOCK
10/21/2009 PLUMBING - PRE SLAB BBENEDON Approved IVRS - Inspection :*
1) TRENCH DRAIN AT B
2) E TRUCK COURT WITH TEST OK TO COVER-WRAP VENT
10/21/2009 ELECTRIC - ABOVE CEILING DSANTACR Approved IVRS - Inspection :*
OK HARD LID A/B MALL ENTRANCE
10/26/2009 RIGHT OF WAY - FINAL MOTERO Approved
10/26/2009 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
10/26/2009 SIGN - FINAL JYBARRA Approved
10/27/2009 FIRE - FINAL LTHOMAS Approved NEW FRONT MALL ENTRANCE OKAY FOR TEMP/PARTAIL C OF O.
10/29/2009 ENGINEERING - FINAL MRUSSO Approved OK FOR TEMP C OF O FOR ENGINEERING ONLY. PERMANENT C OF O NOT TO BE GIVEN UNTIL THE GRADING PERMIT (TO7BU02606) IS COMPLETED AND FINALED.
11/17/2009 BUILDING PRE-SLAB AQUIROZ Approved
11/18/2009 ROOF NAILING AQUIROZ Approved IVRS - Inspection :*
1) ELEVATOR AT BLDG C
12/03/2009 FRAMING JBURGE Approved IVRS - Inspection :*
ELECTRIC ROOM BLDG E OK TO SHEETROCK
12/04/2009 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
1) A,C,D AND E BLDGS DUCT WORK OK, STILL AWAITING START UP, AIR BALANCE, DUCT SMOKE DETECTOR-TEST ALL BLDGS
12/04/2009 SHEET ROCK NAILING JBURGE Approved IVRS - Inspection :*
1) BLDG E, ELECTRIC ROOM-OK TO TAPE INTERIOR AND EXTERIOR WALLS
12/04/2009 PLUMBING - ROOF DRAINS RMYERS Approved IVRS - Inspection :*
1) HANGER WITHIN 18" EACH SIDE OF A COUPLING
2) RECONNECT N/H BAND
12/04/2009 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
12/10/2009 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection :*
1) STEM NORTH OF RFI GL U/0-50' EAST OF N.W. CORNER OF NEW BLDG 0-4"
12/30/2009 STEM WALL/RETAINING WALL AQUIROZ Approved IVRS - Inspection :*
STEM AT WEST SIDE OF REI OK
03/08/2010 BUILDING - PROGRESS AQUIROZ Approved IVRS - Inspection :*
03/18/2010 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
04/22/2010 TEP CLEARANCE - AM JWEATHER Approved ECO CLEARED FOR "SES DPBN" PER D. SANTACRUZ
05/18/2010 OUTDOOR LIGHTING FINAL DSANTACR Approved IVRS - Inspection :*
05/24/2010 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
05/24/2010 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
05/24/2010 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
05/24/2010 FIRE SPKLR - FINAL LTHOMAS Approved
05/24/2010 FIRE - LANE SIGNS LTHOMAS Approved
05/25/2010 BUILDING ABOVE CEILING AQUIROZ Approved
07/15/2010 FIRE - ALARM FINAL LTHOMAS Approved

Documents

File Name Document Type  
TEMP C OF O_10-28-2009.TIF CERT OF OCC VIEW
S804.TIF CONSTRPLANS VIEW
M001.TIF CONSTRPLANS VIEW
M110.TIF CONSTRPLANS VIEW
M111.TIF CONSTRPLANS VIEW
M112.TIF CONSTRPLANS VIEW
M201.TIF CONSTRPLANS VIEW
M202.TIF CONSTRPLANS VIEW
M203.TIF CONSTRPLANS VIEW
M301.TIF CONSTRPLANS VIEW
M302.TIF CONSTRPLANS VIEW
MP110.TIF CONSTRPLANS VIEW
MP210.TIF CONSTRPLANS VIEW
P110.TIF CONSTRPLANS VIEW
P111.TIF CONSTRPLANS VIEW
P112.TIF CONSTRPLANS VIEW
P201.TIF CONSTRPLANS VIEW
REVISED STORM DRAIN.TIF CONSTRPLANS VIEW
P202.TIF CONSTRPLANS VIEW
P203.TIF CONSTRPLANS VIEW
P204.TIF CONSTRPLANS VIEW
DE101.TIF CONSTRPLANS VIEW
DE102.TIF CONSTRPLANS VIEW
E001.TIF CONSTRPLANS VIEW
E002.TIF CONSTRPLANS VIEW
E101.TIF CONSTRPLANS VIEW
E102.TIF CONSTRPLANS VIEW
E103.TIF CONSTRPLANS VIEW
E104.TIF CONSTRPLANS VIEW
E201.TIF CONSTRPLANS VIEW
E202.TIF CONSTRPLANS VIEW
E203.TIF CONSTRPLANS VIEW
E204.TIF CONSTRPLANS VIEW
E301.TIF CONSTRPLANS VIEW
E401.TIF CONSTRPLANS VIEW
E402.TIF CONSTRPLANS VIEW
E501.TIF CONSTRPLANS VIEW
E601.TIF CONSTRPLANS VIEW
E602.TIF CONSTRPLANS VIEW
E603.TIF CONSTRPLANS VIEW
E701.TIF CONSTRPLANS VIEW
E702.TIF CONSTRPLANS VIEW
E703.TIF CONSTRPLANS VIEW
E601.TIF CONSTRPLANS VIEW
E701.TIF CONSTRPLANS VIEW
F001.TIF CONSTRPLANS VIEW
F101.TIF CONSTRPLANS VIEW
F102.TIF CONSTRPLANS VIEW
F103.TIF CONSTRPLANS VIEW
F104.TIF CONSTRPLANS VIEW
F105.TIF CONSTRPLANS VIEW
F106.TIF CONSTRPLANS VIEW
F107.TIF CONSTRPLANS VIEW
L0.01.TIF CONSTRPLANS VIEW
L1.01.TIF CONSTRPLANS VIEW
L2.00.TIF CONSTRPLANS VIEW
L2.01.TIF CONSTRPLANS VIEW
L2.02.TIF CONSTRPLANS VIEW
L2.03.TIF CONSTRPLANS VIEW
L4.01.TIF CONSTRPLANS VIEW
L4.02.TIF CONSTRPLANS VIEW
L4.03.TIF CONSTRPLANS VIEW
L4.04.TIF CONSTRPLANS VIEW
L4.05.TIF CONSTRPLANS VIEW
L5.01.TIF CONSTRPLANS VIEW
L5.02.TIF CONSTRPLANS VIEW
L5.03.TIF CONSTRPLANS VIEW
L5.04.TIF CONSTRPLANS VIEW
L5.05.TIF CONSTRPLANS VIEW
L5.06.TIF CONSTRPLANS VIEW
L5.07.TIF CONSTRPLANS VIEW
L6.00.TIF CONSTRPLANS VIEW
L6.01.TIF CONSTRPLANS VIEW
L6.02.TIF CONSTRPLANS VIEW
L6.03.TIF CONSTRPLANS VIEW
L6.04.TIF CONSTRPLANS VIEW
L6.05.TIF CONSTRPLANS VIEW
L6.06.TIF CONSTRPLANS VIEW
001_W0-0.TIF CONSTRPLANS VIEW
002_W1-0.TIF CONSTRPLANS VIEW
003_W1-1.TIF CONSTRPLANS VIEW
004_W1-2.TIF CONSTRPLANS VIEW
005_W1-3.TIF CONSTRPLANS VIEW
006_W2-0.TIF CONSTRPLANS VIEW
007_W2-1.TIF CONSTRPLANS VIEW
008_W3-0.TIF CONSTRPLANS VIEW
009_W3-1.TIF CONSTRPLANS VIEW
010_W4-0.TIF CONSTRPLANS VIEW
011_W4-1.TIF CONSTRPLANS VIEW
006_ESK 010.TIF CONSTRPLANS VIEW
007_ESK 011.TIF CONSTRPLANS VIEW
008_ESK 012.TIF CONSTRPLANS VIEW
009_ESK 013.TIF CONSTRPLANS VIEW
FIXTURECUTSHEETS.TIF DOCUMENTS VIEW
STRUCCALCS_01 DOCUMENTS VIEW
STRUCCALCS_02 DOCUMENTS VIEW
None DOCUMENTS VIEW