Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/04/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/03/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE ACCESS DOORS TO DAMPERS THROUGH CEILING AND DUCT 2. REPAIR BREAK AWAY ALL OTHER CORRECTIONS DATED 8/28/08 OK |
|
| 08/28/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE ACCESS TO RETAINING ANGLES INSIDE SHAFT FOR INSPECTION 2. PROVIDE MANUFACTURES INSTALLATION INSTRUCTIONS ON FIRE DAMPERS. SPECIFICALLY RETAINING ANGLE SIZE AND GAUGE 3. NOT ALL FIRE DAMPERS HAVE BREAK AWAY |
|
| 08/13/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |