Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03581

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/21/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK NOTES 4/15/10
2) STILL NEED NOTES INSPECTION ON 4/8/10 THRU 4/13/10, EXCEPT PLANTER LIGHTS, LIGHT POLE GROUNDING OK
3) OK ROOF EQUIPMENT EXCEPT UNIT MISSING DISC. SOUTHWEST UNIT
04/16/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CONTINUE INSPECTIONS FOR DPBN, RECEIVED LETTER OF TORQUE, SEE PREVIOUS NOTES, OK ITEMS #2, 3 & 5
2) INSPECTION FOR MAS8 & DSB8 NEED TO FIRE SEAL CONDUIT PENETRATIONS THRU DECK
3) SUPPORT 2" AND 2 1/2 " CONDIUT ABOVE TDP8A
04/15/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE GFI MAIN BREAKER TEST FOR SES FOR DPBN EQUIPMENT, ALSO LABEL EQUIPMENT
2) LETTER OF TORQUE
3) INSTALL BUSHINGS ON FEEDER CONDUIT ENDS IN EQUIPMENT
4) INSPECTIONS FOR SES DPBN AND ASSOC. EQUPMENT DOWNSTREAM
5) BOND XFORMER 225KVA (NUETRAL)
6) CHECK A/C UNITS ON ROOF INSTALL BOND BUSHING AS NECESSARY
7) PANEL DP NEEDS BUSHINGS 250 VOLTS
04/13/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) VERIFY LOADS FOR DP3B REVISE PLAN AS NECESSARY LOADS INCREASED IN FIELD FROM WHAT PLAN SHOWS
2) INSPECTION TODAY FOR DIST. ELECTRIC EQUIPMENT
3) LEDCOR WILL ADDRESS FOUNTAIN CONCERNS
04/09/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHECK GROUNDING FOR LIGHT POLES AND CONDUIT BUSHINGS PER PLAN E703 AND 352.46 NEC
2) ALSO BUSHINGS AT RIGID STEEL CONDUIT ENDS FOR 110V RECEPTS (MUST BE LISTED)
3) REVISE LIGHT FOR FOUNTAINS TO SHOW ACTUAL INSTALL
4) ALL FOUNTAIN LIGHT INSTALLED AND WIRED WITHOUT INSPECTIONS
5) COMPLETE ALL LIGHT IN LIGHT PLANTERS
6) THIS INSPECTION IS FOR 2ND LEVEL C AREA
07/23/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK COLUMNS AT AREA "C"
2) OK PARAPET CONV. OUTLETS ROUGH AREA "A"
06/26/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK HIGH CEILING AREA 'C'
11/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SERVICE
1. SEAL BOTTOM OF SWITCH GEARS
2. NEED PERMANENT LABELING

OK LASHINGS AT SERVICE AND PULL CABINET

ROOF:
1. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING
10/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
-- OK 2 - 4" BUILDING OUT-DATA
-- OK CONDUITS PRIMARY & SECONDARY UNDER CANOPY TO AND FROM SES

1. PLEASE PROVIDE INSTRUCTIONS TO VERIFY BRACING OF CONDUCTORS
2. 230.6 NEEDS TO BE APPLIED
3. PROTECT CONDUCTOR 352.46 & 300.4

RECEIVED LETTER OF TORQUE -
WAITING ON COPY OF GFI TEST
10/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. COMPLETE BONDING
2. INSTALL BUSHINGS AT CONDUIT ENTRIES INTO EQUIP. PROVIDE LETTER OF TORQUE SES 352.46, 300.4-6
3. PROVIDE GFI MAIN BREAKER TEST - 230.95
4. CHECK FOR BRACING PER MANUF.
5. OK 5" PVC SECONDARIES TO CHEESECAKE RESTAURANT
6. UTILITY SIDE CONDUCTORS INSIDE BLD.
10/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NOTE 230.6

OK DEMISING WALL FOREVER 21
OK BRANCH CIRCUIT CONDUITS THROUGH SUNGLASS HUT
09/24/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
6 - 4" LINES APPROX. 12 FROM TRANFORMER TO FUTURE CT ENCLOSURE BOX
07/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ENTRANCE WALL IN VICTORIA'S SECRET (DEMISING)
04/11/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED