Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03581
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/21/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK NOTES 4/15/10 2) STILL NEED NOTES INSPECTION ON 4/8/10 THRU 4/13/10, EXCEPT PLANTER LIGHTS, LIGHT POLE GROUNDING OK 3) OK ROOF EQUIPMENT EXCEPT UNIT MISSING DISC. SOUTHWEST UNIT |
|
| 04/16/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONTINUE INSPECTIONS FOR DPBN, RECEIVED LETTER OF TORQUE, SEE PREVIOUS NOTES, OK ITEMS #2, 3 & 5 2) INSPECTION FOR MAS8 & DSB8 NEED TO FIRE SEAL CONDUIT PENETRATIONS THRU DECK 3) SUPPORT 2" AND 2 1/2 " CONDIUT ABOVE TDP8A |
|
| 04/15/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROVIDE GFI MAIN BREAKER TEST FOR SES FOR DPBN EQUIPMENT, ALSO LABEL EQUIPMENT 2) LETTER OF TORQUE 3) INSTALL BUSHINGS ON FEEDER CONDUIT ENDS IN EQUIPMENT 4) INSPECTIONS FOR SES DPBN AND ASSOC. EQUPMENT DOWNSTREAM 5) BOND XFORMER 225KVA (NUETRAL) 6) CHECK A/C UNITS ON ROOF INSTALL BOND BUSHING AS NECESSARY 7) PANEL DP NEEDS BUSHINGS 250 VOLTS |
|
| 04/13/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VERIFY LOADS FOR DP3B REVISE PLAN AS NECESSARY LOADS INCREASED IN FIELD FROM WHAT PLAN SHOWS 2) INSPECTION TODAY FOR DIST. ELECTRIC EQUIPMENT 3) LEDCOR WILL ADDRESS FOUNTAIN CONCERNS |
|
| 04/09/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECK GROUNDING FOR LIGHT POLES AND CONDUIT BUSHINGS PER PLAN E703 AND 352.46 NEC 2) ALSO BUSHINGS AT RIGID STEEL CONDUIT ENDS FOR 110V RECEPTS (MUST BE LISTED) 3) REVISE LIGHT FOR FOUNTAINS TO SHOW ACTUAL INSTALL 4) ALL FOUNTAIN LIGHT INSTALLED AND WIRED WITHOUT INSPECTIONS 5) COMPLETE ALL LIGHT IN LIGHT PLANTERS 6) THIS INSPECTION IS FOR 2ND LEVEL C AREA |
|
| 07/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK COLUMNS AT AREA "C" 2) OK PARAPET CONV. OUTLETS ROUGH AREA "A" |
|
| 06/26/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK HIGH CEILING AREA 'C' |
|
| 11/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SERVICE 1. SEAL BOTTOM OF SWITCH GEARS 2. NEED PERMANENT LABELING OK LASHINGS AT SERVICE AND PULL CABINET ROOF: 1. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING |
|
| 10/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* -- OK 2 - 4" BUILDING OUT-DATA -- OK CONDUITS PRIMARY & SECONDARY UNDER CANOPY TO AND FROM SES 1. PLEASE PROVIDE INSTRUCTIONS TO VERIFY BRACING OF CONDUCTORS 2. 230.6 NEEDS TO BE APPLIED 3. PROTECT CONDUCTOR 352.46 & 300.4 RECEIVED LETTER OF TORQUE - WAITING ON COPY OF GFI TEST |
|
| 10/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. COMPLETE BONDING 2. INSTALL BUSHINGS AT CONDUIT ENTRIES INTO EQUIP. PROVIDE LETTER OF TORQUE SES 352.46, 300.4-6 3. PROVIDE GFI MAIN BREAKER TEST - 230.95 4. CHECK FOR BRACING PER MANUF. 5. OK 5" PVC SECONDARIES TO CHEESECAKE RESTAURANT 6. UTILITY SIDE CONDUCTORS INSIDE BLD. |
|
| 10/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NOTE 230.6 OK DEMISING WALL FOREVER 21 OK BRANCH CIRCUIT CONDUITS THROUGH SUNGLASS HUT |
|
| 09/24/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 6 - 4" LINES APPROX. 12 FROM TRANFORMER TO FUTURE CT ENCLOSURE BOX |
|
| 07/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ENTRANCE WALL IN VICTORIA'S SECRET (DEMISING) |
|
| 04/11/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |