Permit: T07CM03581

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Approved

Inspection History: ENGINEERING - FINAL

Permit Number - T07CM03581

Inspection Description - ENGINEERING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/20/2010 ENGINEERING - FINAL Approved
10/29/2009 ENGINEERING - FINAL Partial Approval OK FOR TEMP C OF O FOR ENGINEERING ONLY. PERMANENT C OF O NOT TO BE GIVEN UNTIL THE GRADING PERMIT (TO7BU02606) IS COMPLETED AND FINALED.
10/27/2009 ENGINEERING - FINAL Denied 1) PROVIDE A COMPLETE, APPROVED SITE PLAN FOR C OF O FOR INSPECTION.
2) COMPLETE ALL STRIPING PER THE STRIPING PLAN.
3) INSTALL ALL SIGNAGE PER THE SIGN AND STRIPING PLAN.
4) INSTALL ALL DETECTABLE WARNING STRIPS AS SHOWN ON THE APPROVED PLANS.
5) REMOVE AND/OR SEPARATE REMAINING CONSTRUCTION, CONSTRUCTION MATERIAL, EQUIPMENT, AND DEBRIS FROM THE PUBLIC.
6) COMPLETE ALL LANDSCAPING.
7) INSTALL WHEEL STOP AT HC PARKING PLACE IN FRONT OF MACY'S.
8) INSTALL ALL OUTDOOR LIGHTING AND/OR COVER ANY ELECTRIACL CONDUIT/WIRING.
9) INSTALL ALL BIKE PARKING PER PLAN.
10) INSTALL LOADING ZONE NEXT TO CHEESECAKE FACTORY EAST SIDE.
11) 2- HC PARKING SPOTS NEAR MACYS DO NOT MEET THE <2% CROSS-SLOPE PER ADAAG AND ANSI.
10/15/2009 ENGINEERING - FINAL Not ready for Inspection Site not ready