Inspection Status: Approved
Inspection History: PLUMBING - ROOF DRAINS
Permit Number - T07CM03581
Inspection Description - PLUMBING - ROOF DRAINS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2010 | PLUMBING - ROOF DRAINS | Approved | IVRS - Inspection :* 1) RECEIVED REVISED APPROVED PLAN |
|
| 12/04/2009 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* 1) HANGER WITHIN 18" EACH SIDE OF A COUPLING 2) RECONNECT N/H BAND |
|
| 11/17/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1) BLDG 'B' OVERHEAD ROOF DRAIN AND OVERFLOW DRAINS OK 2) WATER TEST OK |
|
| 11/05/2009 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* | |
| 10/08/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1) 15" N/H RAIN WATER LEADERS CONNECTED TO EXISTING AND TERMINATED AT MAN HOLE FOR BLDG "B" ONLY |
|
| 08/25/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1) RWLS FROM S37 THR T36 |
|
| 08/24/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* | |
| 08/07/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1) BLDG 'E' ROOF DRAINS UNDERGROUND 8" PVC FROM BLDG, 6" THRU STEM WALL AND UP, CONNECTED TO 10" COMBO PIPING STOPS JUST DOWN STREAM OF 10" COMBO |
|
| 07/28/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1) BLDG "A" OVERHEAD-OK |
|
| 07/27/2009 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* | |
| 07/24/2009 | PLUMBING - ROOF DRAINS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLDG "A" RAIN WATER LENDERS REDUCING 16" TO 12" IS NOT PERMITTED 2) GALVANIZED REDUCER NOT APPROVED DRAINAGE FITTING AND NOT PERMITTED UNDER FLOOR RAFTER COUPLING NOT APPROVED CONNECTOR 2) PIPING TO HAVE 2 PERCENT GRADE |
|
| 07/22/2009 | PLUMBING - ROOF DRAINS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SWEEPS AS REQUIRED 2) PROVIDE FULL SIZE WYE AT 4 X 4 X 6 CONN. |
|
| 07/02/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1) 4" N/H CAST IRON RISING UP ALONG TWO OUTER COLUMNS OK 2) 4-4" N/H ROOF DRAINS INSTALLED UNDER HIGH ROOF TO BELOW CEILING OK |
|
| 06/23/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 2 - 4" RAIN WATER LEADERS FROM HIGH ROOF AT BLDG. "C" TO P.O.C UNDERGROUND OK TO COVER UP TO TEN FEET ONLY |
|
| 11/24/2008 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 4" AND 6" SCH40 PVC RAIN LEADERS TERMINATING AT MANHOLE BETWEEN BLDG. B & C |
|
| 11/18/2008 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* BELL AND SPIGOT SDR35 NOT APPROVED FOR ROOF DRAINS BELOW GRADE |
|
| 11/12/2008 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1. 6" PVC SANITARY SEWER INSTALLED INTO MANHOLE AT BLDG. "D" 10" PVC STORM DRAIN INSTALLED INTO CATCH BASIN 2. 6" PVC SANITARY SEWER TIED INTO MANHOLE AT BLDG "B" OK |
|
| 10/08/2008 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* BLDG "A" - 12" SCH 40 PVC STORM DRAIN - FROM JUST OUTSIDE MANHOLE TO STUB UP AT BLDG "A" 2. BLDG. "C" UNDER FLOOR FOR VICTORIA'S SECRET BLDG "D" 6" SEWER FROM P.O.C AT BLDG TO CROSSING AT 10" STORM DRAIN, INSTALLED PER REDLINES OK TO COVER THIS SECTION |
|
| 10/02/2008 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1. NEED TO SEE POINT OF CONNECTION TO EXISTING OVERHEAD 2ND FLOOR 2. WATER TEST OK 3. HANGERS REQUIRED AT EACH CHANGE OF DIRECTION |
|
| 09/18/2008 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* | |
| 08/21/2008 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* ROOF DRAIN AND OVERFLOW DRAIN TO ROOF OK WATER TEST OK |
|
| 08/07/2008 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1) 2"-6" PVC RAIN HEADERS STABBED INTO LOWER LEVEL AND ON 6" TEST RISER ALONG COLUMN OK 2) WATER TEST OK 3) OK TO COVER THIS AREA |