Inspection History: PLUMBING - ROOF DRAINS

Permit Number - T07CM03581

Inspection Description - PLUMBING - ROOF DRAINS

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2010 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :*
1) RECEIVED REVISED APPROVED PLAN
12/04/2009 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
1) HANGER WITHIN 18" EACH SIDE OF A COUPLING
2) RECONNECT N/H BAND
11/17/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) BLDG 'B' OVERHEAD ROOF DRAIN AND OVERFLOW DRAINS OK
2) WATER TEST OK
11/05/2009 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
10/08/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) 15" N/H RAIN WATER LEADERS CONNECTED TO EXISTING AND TERMINATED AT MAN HOLE FOR BLDG "B" ONLY
08/25/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) RWLS FROM S37 THR T36
08/24/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
08/07/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) BLDG 'E' ROOF DRAINS UNDERGROUND 8" PVC FROM BLDG, 6" THRU STEM WALL AND UP, CONNECTED TO 10" COMBO PIPING STOPS JUST DOWN STREAM OF 10" COMBO
07/28/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) BLDG "A" OVERHEAD-OK
07/27/2009 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
07/24/2009 PLUMBING - ROOF DRAINS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLDG "A" RAIN WATER LENDERS REDUCING 16" TO 12" IS NOT PERMITTED
2) GALVANIZED REDUCER NOT APPROVED DRAINAGE FITTING AND NOT PERMITTED UNDER FLOOR RAFTER COUPLING NOT APPROVED CONNECTOR
2) PIPING TO HAVE 2 PERCENT GRADE
07/22/2009 PLUMBING - ROOF DRAINS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE SWEEPS AS REQUIRED
2) PROVIDE FULL SIZE WYE AT 4 X 4 X 6 CONN.
07/02/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) 4" N/H CAST IRON RISING UP ALONG TWO OUTER COLUMNS OK
2) 4-4" N/H ROOF DRAINS INSTALLED UNDER HIGH ROOF TO BELOW CEILING OK
06/23/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
2 - 4" RAIN WATER LEADERS FROM HIGH ROOF AT BLDG. "C"
TO P.O.C UNDERGROUND OK TO COVER UP TO TEN FEET ONLY
11/24/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
4" AND 6" SCH40 PVC RAIN LEADERS TERMINATING
AT MANHOLE BETWEEN BLDG. B & C
11/18/2008 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
BELL AND SPIGOT SDR35 NOT APPROVED FOR ROOF DRAINS BELOW GRADE
11/12/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1. 6" PVC SANITARY SEWER INSTALLED INTO MANHOLE
AT BLDG. "D"
10" PVC STORM DRAIN INSTALLED INTO CATCH BASIN
2. 6" PVC SANITARY SEWER TIED INTO MANHOLE AT
BLDG "B" OK
10/08/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
BLDG "A" - 12" SCH 40 PVC STORM DRAIN - FROM JUST OUTSIDE MANHOLE TO STUB UP AT BLDG "A"
2. BLDG. "C" UNDER FLOOR FOR VICTORIA'S SECRET
BLDG "D" 6" SEWER FROM P.O.C AT BLDG TO CROSSING AT 10" STORM DRAIN, INSTALLED PER REDLINES

OK TO COVER THIS SECTION
10/02/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1. NEED TO SEE POINT OF CONNECTION TO EXISTING OVERHEAD 2ND FLOOR
2. WATER TEST OK
3. HANGERS REQUIRED AT EACH CHANGE OF DIRECTION
09/18/2008 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
08/21/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
ROOF DRAIN AND OVERFLOW DRAIN TO ROOF OK
WATER TEST OK
08/07/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) 2"-6" PVC RAIN HEADERS STABBED INTO LOWER LEVEL AND ON 6" TEST RISER ALONG COLUMN OK
2) WATER TEST OK
3) OK TO COVER THIS AREA