Permit: T06CM04873
Permit Details
Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
8265 S HOUGHTON RD #101
Address NEW:
8265 S HOUGHTON RD #101
Apply Date:
08/31/2006
Applicant:
METRO PERMIT EXPRESS, INC *C
Description:
TI: DENTAL OFFICE- FIRST TENANT IN SHELL
Contractors:
- CAYLOR CONSTRUCTION COMPANY , RO
Permit Reviews
Permit Number - T06CM04873
Permit Status: C of o
Permit Description: TI: DENTAL OFFICE-
FIRST TENANT IN SHELL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/05/2007 | POST 3RD PARTY REVIEW | 04/06/2007 | COMPLETED |
| 04/09/2007 | POST 3RD PARTY REVIEW | 04/10/2007 | COMPLETED |
| 08/31/2006 | PLANS OK TO SUBMIT - 3RD PARTY | 08/31/2006 | COMPLETED |
| 08/31/2006 | 3RD PARTY REVIEW-COMMERCIAL TI | 04/05/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM04873
Permit Status: C of o
Permit Description: TI: DENTAL OFFICE-
FIRST TENANT IN SHELL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/31/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T06CM04873
Permit Description: TI: DENTAL OFFICE-
FIRST TENANT IN SHELL
Total Completed Inspections - 32
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2007 | ELECTRIC - TEMPORARY SERVICE | RJIROUDE | Approved | IVRS - Inspection :* 1) TEMP SERVICE FOR CONSTRUCTION POWER |
| 08/15/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | TMPP CLEARED FOR #101 PER R. JIROUDEK |
| 08/17/2007 | ELECTRIC - UFER | RJIROUDE | Approved | IVRS - Inspection :* 1. OK 3/0 COPPER TO REBAR IN FOOTING GEC 2. OK 3/0 COPPER TO REBAR IN FOOTING WATER BOND 3. OK 3/0 COPPER TO REBAR IN FOOTING SPRINKLER BOND 4. OK #6 COPPER TO REBAR IN FOOTING FOR TELEPHONE |
| 08/21/2007 | EXCAVATION/LAYOUT REBAR & ZON | GDABBS | Approved | IVRS - Inspection :* |
| 09/20/2007 | ELECTRIC - UNDERGROUND | RJIROUDE | Approved | IVRS - Inspection :* 1) OK 3-2 1/2" PVC FROM SES TO PANEL LOCATIONS 2) OK 3/4" RIGID CONDUIT UNDER SLAB FOR POWER 3) OK 2" PVC UNDER SLAB FOR TELEPHONE/DATA |
| 09/26/2007 | BUILDING PRE-SLAB | GDABBS | Approved | IVRS - Inspection :* TI @ SOUTH END NOT TO BE POURED UNDER SHELL PERMIT |
| 11/27/2007 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection :* 1) DWV WATER TEST THRU ROOF AND WATER PIPING OK 2) CALL IN FOR CLOSET FLANGE INSPECTION |
| 11/27/2007 | PLUMBING - ROUGH, SOIL | RRICH | Approved | IVRS - Inspection :* |
| 11/28/2007 | FRAMING | GDABBS | Approved | IVRS - Inspection :* |
| 12/11/2007 | PLUMBING - ABOVE CEILING | RRICH | Approved | IVRS - Inspection :* BRAZING OF NITROUS OXIDE, OXYGEN, COMPLETED AIR |
| 12/11/2007 | PLUMBING - MEDICAL GAS/FINAL | RRICH | Approved | IVRS - Inspection :* |
| 12/19/2007 | PLUMBING - MEDICAL GAS/TEST | RRICH | Approved | IVRS - Inspection :* TESTING IN PLACE FOR ALL MED GAS PIPING NEED 3RD PARTY VERIFICATION SIGNED OFF ON PERMIT CARD NEED COMPLETION OF LABELING |
| 12/27/2007 | ELECTRIC - INTERMEDIATE | RJIROUDE | Approved | IVRS - Inspection :* 1) OK WALLS |
| 02/20/2008 | SHEET ROCK NAILING | GDABBS | Approved | IVRS - Inspection :* |
| 02/20/2008 | SHEET ROCK NAILING | GDABBS | Approved | IVRS - Inspection :* |
| 02/26/2008 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
| 02/26/2008 | BUILDING ABOVE CEILING | GDABBS | Approved | IVRS - Inspection :* CORRECTION OF NUMBER 1 FROM PREVIOUS INSPECTION COMPLETED |
| 03/12/2008 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 03/12/2008 | NPPO - FINAL | ACONNOR | Approved | |
| 03/12/2008 | LANDSCAPE - FINAL | ACONNOR | Approved | |
| 03/12/2008 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | PER EMAIL |
| 03/14/2008 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 03/14/2008 | FIRE - FINAL | LTHOMAS | Approved | |
| 03/26/2008 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* TESTED DUCT SMOKE DETECTORS OK FOR FINAL |
| 03/26/2008 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
| 03/26/2008 | STUCCO MESH | GDABBS | Approved | IVRS - Inspection :* |
| 03/26/2008 | ELECTRIC - ABOVE CEILING | RJIROUDE | Approved | IVRS - Inspection :* |
| 03/27/2008 | ELECTRIC - FINAL | RJIROUDE | Approved | IVRS - Inspection :* |
| 04/02/2008 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* |
| 04/23/2008 | ENGINEERING - FINAL | NKALAHAR | Approved | CP-COMPLETE ALL ASPHALT PATCHES CP-CLEAN UP WASH OUT AND CONSTRUCTION DEBRIS S OF SCREEN WALL CP*-ADDRESS ADA ISSUES-APPROVED REVISION MUST BE READY TO BUILD BEFORE TEMP C OF O. THIS INCLUDES H/C PARKING STALLS TOO STEEP ON N SIDE FO BLDG AND ADA ACCESSIBLE ROUTE FROM ROW TO 8265. CP-INSTALL BIKE LOCKERS PER PLAN (DEV PLAN)--2 BIKE LOCKERS INSTALLED NE CORNER OF BLDG TOTAL OF 4 EACH CLASS 1 + 2 INSTALLED ON SITE CP*REVISED DEVELOPMENT PLAN ON SITE-NO REVISED GRADING PLAN |
| 04/23/2008 | ENGINEERING - FINAL | NKALAHAR | Approved | |
| 04/23/2008 | BUILDING - FINAL | GDABBS | Approved | IVRS - Inspection :* |