Permit Number: T06CM04873
Parcel: 14117014C

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM04873
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/06/2007 GERRY KOZIOL WWM REVIEW Denied
04/06/2007 MARTIN BROWN FIRE REVIEW Denied IFC 3006.2 - (Compressed gasses intended for inhalation for dentistry) shall be stored in areas dedicated to teh storage of such gasses.

TFC Modifications 508.5.2 - Required installations: Hydrants shall be located within 300 feet of all portions of structures.

Be advised: sprinkler plans shall be seperately.
04/06/2007 ROBERT SHERRY WATER REVIEW Denied Provide approval from Tucson Water for the use of a 1" water meter for a demand flow greater than 25 GPM.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2007 DELMA ROBEY APPROVAL SHELF Completed
04/06/2007 DELMA ROBEY OUT TO CUSTOMER Completed
04/06/2007 DELMA ROBEY REJECT SHELF Completed