Permit: T06CM04873

Parcel: 14117014C

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
02/26/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
02/21/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- DO NOT SCREW METAL FITTINGS INTO PLASTIC
CONDENSATE PANS.
- PROVIDE BUSHINGS FOR REFER LINE CONNECTIONS
- PROVIDE MIN. 1/8" PER FT. SLOPE ON ALL CONDENSATE DRAIN LINES
- FINISH CONNECTIONS ABOVE CEILING
01/23/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
INSPECTED SUPPLY & EXHAUST DUCTS IN HARD LID AREAS
AND SOFFITS. OK TO COVER.