Permit: T06CM04873

Parcel: 14117014C

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
03/26/2008 ELECTRIC - UFER Approved IVRS - Inspection :*
08/17/2007 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1. OK 3/0 COPPER TO REBAR IN FOOTING GEC
2. OK 3/0 COPPER TO REBAR IN FOOTING WATER BOND
3. OK 3/0 COPPER TO REBAR IN FOOTING SPRINKLER BOND
4. OK #6 COPPER TO REBAR IN FOOTING FOR TELEPHONE
08/16/2007 ELECTRIC - UFER Denied IVRS - Inspection :
The grounding electrode conductor is not installed per code.| 220*
1. GROUND CLAMPS NEED TO BE LISTED & MARKED FOR USE ON REBAR & SIZE OF REBAR.
ALSO, NEEDS TO BE MARKED & LISTED FOR DIRECT BURY
NEC 250.70