Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2008 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 08/17/2007 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1. OK 3/0 COPPER TO REBAR IN FOOTING GEC 2. OK 3/0 COPPER TO REBAR IN FOOTING WATER BOND 3. OK 3/0 COPPER TO REBAR IN FOOTING SPRINKLER BOND 4. OK #6 COPPER TO REBAR IN FOOTING FOR TELEPHONE |
|
| 08/16/2007 | ELECTRIC - UFER | Denied | IVRS - Inspection : The grounding electrode conductor is not installed per code.| 220* 1. GROUND CLAMPS NEED TO BE LISTED & MARKED FOR USE ON REBAR & SIZE OF REBAR. ALSO, NEEDS TO BE MARKED & LISTED FOR DIRECT BURY NEC 250.70 |