Permit: T06CM04873

Parcel: 14117014C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/27/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/26/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/26/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SECURE BOXES & LIGHTS, MC/ACF CABLE
2. INSTALL ALL MOUNTING SCREWS IN INDUSTRIAL COVERS
3. HAVE BROKEN FLEX & 90 DEG. FLEX CONNECTORS TO BE ACCESSIBLE
03/24/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FINISH WORK
2. HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE SPACE
3. MISSING PLATES. BROKEN FLEX. RECEPTS NO POWER, NEED PROPER WIRING TO EXAM LIGHTS. STRAP MC/HCF CABLE USE PROPER MC/HCF CONNECTORS, MISSING SCREWS ON INDUSTRIAL COVERS, WIRING DISCONNECTS ON DISCONNECTING UNITS. LOW VOLTAGE & HIGH VOLTAGE IN SAME BOX. THIS IS NOT A COMPLETE LIST.
4. RECALL WHEN READY