Permit: T06CM04873

Parcel: 14117014C

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/26/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
TESTED DUCT SMOKE DETECTORS
OK FOR FINAL
03/24/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- SEAL DUCT CONNECTIONS TO FAN COILS
- DRAIN PANS NOT FITTING CORRECTLY UNDER FAN COILS
- PROVIDE A SMOKE TEST ON DUCT SMOKE DETECTOR
- PERMANENTLY I.D EQUIPMENT ON ROOF
- 2 CONDENSORS NOT FUSED CORRECTLY
- 2 DISCONNECTS INSTALLED ON WRONG CONDENSORS
- SECURE MINI-SPLIT CONDENSOR
- AIR BALANCE OK