Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address:
2480 N ORACLE RD
Address NEW:
2480 N ORACLE RD
Apply Date:
10/18/2005
Applicant:
SAKELLAR, C NICHOLAS
Description:
C OF O FOR RESTAURANT ONLY
Architects:
  • SAKELLAR, C NICHOLAS
Contractors:
  • FARWEST DEVELOPMENT AND CONSTRUCTION OF THE SOUT

Permit Reviews

Permit Number - T05CM05315
Permit Status: C of o
Permit Description: C OF O FOR RESTAURANT ONLY
Start Date Submittal Complete Date Status  
01/12/2007 3RD PARTY REVIEW-REVISION/OTHER 01/13/2007 COMPLETED Review Details
01/13/2007 3RD PARTY REVIEW-REVISION/OTHER 04/10/2007 COMPLETED Review Details
02/10/2006 POST 3RD PARTY REVIEW 03/23/2006 COMPLETED Review Details
04/12/2006 RESUBMITTAL 05/24/2006 COMPLETED Review Details
10/18/2005 PLANS OK TO SUBMIT - 3RD PARTY 10/20/2005 COMPLETED Review Details
10/20/2005 3RD PARTY REVIEW-COMMERCIAL 02/10/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM05315
Permit Status: C of o
Permit Description: C OF O FOR RESTAURANT ONLY
Total Outstanding Activity Conditions - 1
Date Name
10/18/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM05315
Permit Description: C OF O FOR RESTAURANT ONLY
Total Completed Inspections - 50
Date Description Inspector Results Comments
06/15/2006 ELECTRIC - TEMPORARY SERVICE CCLEMENS Approved IVRS - Inspection :*
07/10/2006 ELECTRIC - CONSTRUCTION POWER RMAJUTA Approved IVRS - Inspection :*
07/25/2006 SITE - SEWER RMYERS Approved IVRS - Inspection :*
08/22/2006 REINFORCED MASONRY PRE-GROUT AQUIROZ Approved IVRS - Inspection :*
TOP OUT MAIN BUILDING
09/18/2006 ROOF NAILING AQUIROZ Approved IVRS - Inspection :*
EXCLUDES NORTHEAST ROOM
09/18/2006 EXT METAL CLIPS/EXT SHEATHING AQUIROZ Approved IVRS - Inspection :*
09/21/2006 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection :*
FROM COLUMNS TO COLUMNS ONLY
10/04/2006 PLUMBING - ROOF DRAINS RMYERS Approved IVRS - Inspection :*
10/16/2006 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
10/19/2006 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*
10/25/2006 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*
PARTIAL OK HARD CEILINGS
RMS. 117, 116, 115, 103, 106
10/26/2006 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*
TYPE 1 HOODS NON-COMBUSTIBLES WALL AT REAR
RESTROOM LIDS, OK TO COVER DRY STORAGE
OK TO WRAP 10X10 & 12 EX. DUCT
10/26/2006 FRAMING AQUIROZ Approved IVRS - Inspection :*
10/27/2006 SHEET ROCK NAILING JBURGE Approved IVRS - Inspection :*
11/02/2006 MECHANICAL - PROGRESS CWILLIAM Approved IVRS - Inspection :*
1) TYPE I EXHAUST HOOD 16 GA. BLK IRON DUCTS
2) OK TO WRAP 3 M INSUL.
3) NOTE: CONTINUE WRAP UP INTO TOP OF CURB, NOT JUST TO WOOD/SHEATHING
11/08/2006 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved Visual only - no presure test
11/13/2006 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
1. IT APPEARS THAT YOU HAVE MODIFIED THE PLUMBING IN A COUPLE OF PLACES.
NO REDLINES ON SITE
NO REVISED APPROVED PLAN REVISION.
2. N/H BANDS NOT APPROVED FOR ABS.
3. NO TEST ON MODIFIED PLUMBING.
4. HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP TRAP ARM MAY ONLY CHANGE DIRECTION 90 DEG.
5. PLUMBER TO CAP OFF ALL OPEN PIPING ASAP!!
11/14/2006 PLUMBING - BACK WATER VALVE RMYERS Approved IVRS - Inspection :*
11/14/2006 PLUMBING - SEWER HCS CONNECT RMYERS Approved IVRS - Inspection :*
11/14/2006 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*
11/15/2006 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
INSTALL GLASS FIBER INSULATION WITH ASJ (LIKE THE REST) ON HOT WATER SYSTEM.
11/22/2006 EXCAVATION/LAYOUT REBAR & ZON GDABBS Approved IVRS - Inspection :*
TWO LIGHT POLE BASES
11/22/2006 ELECTRIC - UNDERGROUND CCLEMENS Approved IVRS - Inspection :*
1) INSPECTION FOR EXTERIOR PARKING AREA POLES
2) RACEWAYS DO NOT HAVE PROPER BURIAL DEPTH-NEC 300.5 24" MAKE SURE IN PARKING AREAS
3) PROVIDE LETTER FROM ARCHITECT CONCERNING DELETION OF POLES
4) OK COVER 2 CENTER AREA POLES
11/22/2006 ELECTRIC - OUTDOOR LIGHTING CCLEMENS Approved IVRS - Inspection :*
12/01/2006 MECHANICAL - ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
EXCLUDES DINING AREA
12/08/2006 STEM WALL/RETAINING WALL AALEGRIA Approved IVRS - Inspection :*
PARTIAL @ DUMPSTER ENCLOSURE
12/11/2006 ELECTRIC - UFER CCLEMENS Approved IVRS - Inspection :*
1) PROVIDE APPROVAL LETTER FROM ENGINEER CONCERNING DELETION OF UFER
2) ROUTE NEUTRAL TO EACH SERVICE DISCONNECT AND BOND TO ENCLOSURE-NEC 250.24B
3) NEED TO POST BOND FOR POWER
4) MAKE SURE YOU LOCK OUT ANY OPEN WIRING THAT MAY BECOME ENERGIZED
12/11/2006 ELECTRIC - TEMP POWER FOR TEST CCLEMENS Approved IVRS - Inspection :*
12/11/2006 ELECTRIC - CABLE DROP CCLEMENS Approved IVRS - Inspection :*
12/11/2006 ELECTRIC - ABOVE CEILING CCLEMENS Approved IVRS - Inspection :*
12/22/2006 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
OK FOR GAS CLEARANCE
SCHEDULE FINAL AFTER POWER IS ON
12/22/2006 U VALUE FOR WINDOW AQUIROZ Approved IVRS - Inspection :*
12/22/2006 FIRE SPKLR - FINAL LTHOMAS Approved
01/09/2007 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
01/09/2007 NPPO - FINAL ACONNOR Approved
01/09/2007 LANDSCAPE - FINAL ACONNOR Approved
01/11/2007 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
01/11/2007 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
01/16/2007 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :*
01/16/2007 OUTDOOR LIGHTING FINAL CCLEMENS Approved IVRS - Inspection :*
01/18/2007 ENGINEERING - FINAL MRUSSO Approved
01/19/2007 PLUMBING - GAS PRESS TEST FNL RMYERS Approved IVRS - Inspection :*
01/25/2007 STUCCO MESH JBURGE Approved IVRS - Inspection :*
01/26/2007 FIRE - KITCHEN EXH HOOD FINAL LLAKEY Approved
01/26/2007 FIRE - FINAL LLAKEY Approved
01/29/2007 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
OK C OF O
01/31/2007 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK FOR C OF O
S.T.O.I
01/31/2007 HEALTH DEPT - FINAL 724-7908 JTERREL Approved PER HEALTH INSP
04/03/2007 MECHANICAL - HOODS JMILITEL Approved JOB CARD
04/03/2007 SIGN - FINAL DCAPPLE Approved ISSUE THE C OF O FOR ONLY THE PORTION OF THE SITE THE RESTAURANT IS ON. MAKE SURE THE C OF O SPECIFIES THAT IT IS ONLY FOR THAT PORTION OF THE SITE THAT THE RESTAURANT IS ON.