Permit: T05CM05315

Parcel: 10714208A


Addresses:

2480 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM05315

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/24/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/23/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/19/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROVIDE INSPECTION HISTORY FOR SEWER
2. PROVIDE INSPECTION HISTORY FOR GAS
NOTE: I DO NOT HAVE TIME TO ORGANIZE YOUR PAPERWORK PLEASE HAVE ALL NECESSARY PAPERWORK READILY AVAILABLE AT TIME OF INSPECTION.
3. REVISED PLAN ON SITE 03005 ROUGH APP
4. GAS PRESSURE TEST OK
LEFT GAS CARD

SW GAS 889-1888
11/15/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
INSTALL GLASS FIBER INSULATION WITH ASJ (LIKE THE REST) ON HOT WATER SYSTEM.
11/14/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLUMBING MODIFICATION REDLINED ON PLAN
WILL REQUIRE A REVIEW AND REVISED PLAN.
2. 1/4 BEND NEEDS TO BE A SWEEP
3. INSULATE HOT WATER PIPING
4. REQUIRE REVISED PLAN FOR REDLINED UNDERGROUND.
10/19/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CORRECTIONS MADE OK
OK TO COVER ALL AREAS
10/16/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ALL PIPING PASSING THRU MASONRY TO BE WRAPPED.
2. ABS NOT APPROVED IN EXPOSED EXTERIOR LOCATION
(G.I VENT)
3. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.
4. SCREW DOWN CLOSET FLANGES.
5. TEST DOMESTIC WATER PIPING TO 100# FOR 24 HRS.
10/15/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PLAN CALLS FOR 2" RPA
2. ABS MAY NOT BE DIRECTLY EMBEDDED IN MASONRY.
3. OVERHEAD ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN 4' BETWEEN HANGERS. SCREW DOWN FLANGES.
10/04/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. WELD PIPE REQUIRES 60# TEST
2. NO RPPBP INSTALLED -- TEMP HOSE BIBBS TO HAVE VACUUM BREAKERS.
3. ROOF DRAINS WATER TEST OK
4. PLUMBING IS TO BE INSTALLED IN A WORKMANSHIP LIKE MANNER TO ACCEPTABLE ENGINEERING PRACTICES AND PER THE APPROVAL PLAN. CHANGES ARE TO BE ACCOMPANIED WITH AT LEAST REDLINES.
5. READ PLUMBING PLAN NOTES -- THEY WILL BE ENFORCED.