Permit: T05CM05315

Parcel: 10714208A


Addresses:

2480 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM05315

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/31/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK FOR C OF O
S.T.O.I
01/30/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SEE NOTE #1 FROM 1/26/07
2. PROVIDE NSF LISTING FOR HOSE SUPPLY
01/29/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
YOU BEEN TOLD THREE TIMES THAT A 1/2" I.D BACKFLOW DEVICE REQUIRES 1/2" I.D SUPPLY
REDUCING EACH SIDE OF THE DEVICE IS NOT ACCEPTABLE
INSTALL FULL 1/2" SUPPLY TO THE DEVICE
ON THE OUTLET SIDE YOU MAY REDUCE TO 3/8"
CONTRACTOR TO PAY REINSPECTION FEE
01/26/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. DOUBLE WYE MAY NOT BE INSTALLED IN THE HORIZONTAL POSITION.
2. 1/2" RIPS BACKFLOW DEVICES REQUIRE FULL 1/2" SUPPLY
01/24/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. INSULATION ON TEPID WATER TO HOSE REEL AND RPBFP OK
2. URINAL LOWERED TO ADA HEIGHT OK - SUBJECT TO BLDG. INSP.
3. DO NOT CALL FINAL UNTIL IT IS READY.
01/23/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
INSTALL THE INSULATION IN A WORKMANSHIP LIKE MANNER
CONFORMING TO INSTALLATION STANDARD.
01/18/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
HOSE REEL WILL REQUIRE BACKFLOW PROTECTION = POLLUTION
01/12/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. A GAS CARD MAY BE LEFT WHEN CONTRACTOR POSTS A BOND, AND ALL OTHER REQUIRED INSPECTIONS HAVE BEEN APPROVED.
2. CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTIONS THIS INCLUDES ALL REQUIRED PAPERWORK. NOT BEING READY WILL CAST YOU A REINSPECTION FEE.
3. I HAVE MENTIONED SEVERAL TIMES BEFORE - THE PLUMBER MUST INSTALL PER PLAN.
01/11/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
(REQ. GAS CLEARANCE)
1. NEED SAFETY CABLES INSTALLED ON ROLLING GAS APPLIANCES.
2. NEED OK FROM MECH. INSPECTOR AND ALL APPLIANCES INSTALLED FOR GAS SERVICE.