Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM05315
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* PICKED UP AIR BALANCE REPORT OK FOR FINAL |
|
03/29/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* AIR BALANCE ALL HOODS & EXHAUST FANS |
|
01/24/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE AN AIR BALANCE REPORT APPROVED BY THE ENGINEER. OK TO FILE FOR TEMP C OF O |
|
01/22/2007 | MECHANICAL - FINAL | Partial Approval | CORRECTIONS PROGRESSING | |
01/19/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE FRESH AIR INTAKES. 2. PROVIDE AIR BALANCE REPORTS FOR ALL EQUIPMENT. 3. INSULATE REFER LINES ON ROOF. 4. PROVIDE GREASE CUPS ON EXHAUST FANS. 5. EXTEND SEWER VENTS 2' ABOVE EVAP. COOLER & FRESH AIR INTAKES. 6. GAS FLEX CONNECTORS NOT SIZED CORRECTLY. 7. A/C REQUIRES A DUCT SMOKE DETECTOR W/AUDIBLE AND VISIBLE ALARMS. 8. PROVIDE STAINLESS STEEL WITHIN 18" OF HOODS. |
|
12/22/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* OK FOR GAS CLEARANCE SCHEDULE FINAL AFTER POWER IS ON |