Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T05CM05315
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
11/14/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
07/25/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. 3" FOR MOP SINK ON GREASE WASTE LINE OK SUBJECT TO REVISED PLAN REDLINES ON P-101 2. INTERCEPTOR OK TO COVER |
|
07/20/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* INTERCEPTOR INSPECTION INLET OK SUBJECT TO TEST 3" G.W. TO MOP SINK (CHANGE ORDER) INSTALLED OK TO COVER SUBJECT TO APPROVED PLAN. |
|
07/05/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
07/03/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* PLUMBER NEEDS TO MAKE CORRECTIONS BACKPITCHED TRAP ARMS BACKPITCHED VENTS. NOTE: ONLY ONE THIRD OF THE TOTAL DEVELOPED LENGTH OF A VENT MAY BE INSTALLED IN THE HORIZONTAL POSITION. VENT UNDER SLAB TO HAVE 1/4" PITCH. SDR 35 IS NOT AN APPROVED MATERIAL FOR UNDER A BLDG. |
|
06/28/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) DRAINS IN PATIO AREA OKAY TO COVER |