Permit: T05CM05315

Parcel: 10714208A


Addresses:

2480 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM05315

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
01/19/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
11/14/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
07/25/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. 3" FOR MOP SINK ON GREASE WASTE LINE OK
SUBJECT TO REVISED PLAN REDLINES ON P-101
2. INTERCEPTOR OK TO COVER
07/20/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
INTERCEPTOR INSPECTION
INLET OK SUBJECT TO TEST
3" G.W. TO MOP SINK (CHANGE ORDER) INSTALLED
OK TO COVER SUBJECT TO APPROVED PLAN.
07/05/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
07/03/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
PLUMBER NEEDS TO MAKE CORRECTIONS
BACKPITCHED TRAP ARMS
BACKPITCHED VENTS.
NOTE: ONLY ONE THIRD OF THE TOTAL DEVELOPED LENGTH OF A VENT MAY BE INSTALLED IN THE HORIZONTAL POSITION. VENT UNDER SLAB TO HAVE 1/4" PITCH.
SDR 35 IS NOT AN APPROVED MATERIAL FOR UNDER A BLDG.
06/28/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) DRAINS IN PATIO AREA OKAY TO COVER