Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T05CM05315
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
11/22/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) INSPECTION FOR EXTERIOR PARKING AREA POLES 2) RACEWAYS DO NOT HAVE PROPER BURIAL DEPTH-NEC 300.5 24" MAKE SURE IN PARKING AREAS 3) PROVIDE LETTER FROM ARCHITECT CONCERNING DELETION OF POLES 4) OK COVER 2 CENTER AREA POLES |
|
11/17/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* SERVICE & SIGN RACEWAYS (STUB) - MAKE SURE WARNING RIBBON INSTALLED - NEC 300.5 D3 HAVE ENGINEER PROVIDE LETTER (SEALED) AS TO WHAT HE WANTS DONE CONCERNING UFER THAT WAS LEFT OUT FOR BOTH BUILDINGS. |
|
09/12/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK COVER BRANCH CKT RACEWAYS IN EXTERIOR SLAB. |
|
07/14/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK UNDER EAST SLAB (MAIN KITCHEN AREA) |