Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM05315
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/11/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/08/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
12/07/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. UP SIDE EQUIPMENT GROUND WHERE REQUIRED BY NEC 250.122 B 2. LOW VOLTAGE WIRING CORRECTIONS NOT MADE 3. CHECK RACEWAY FILL - NEC CHAPTER 9 TABLE 1 4. FINISH ALL WIRING ABOVE CEILING |
|
12/05/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE OVERFILLED J-BOXES -- NEC 314.16 2. GROUND ALL EQUIPMENT WITH EQUIPMENT GROUNDING CONDUCTOR -- NEC 250.148 3. SEAL RACEWAYS FOR WALKINS -- NEC 300.7 4. SUPPORT WIRES FOR FIXTURES TO BE AT OPPOSITE CORNERS. 5. LOW VOLTAGE WIRING TO BE SUPPORTED BY STRUCTURE AND NOT OTHER EQUIPMENT AND RAN IN A NEAT AND WORKMANLIKE MANNER -- NEC 300.11 B, NEC 800.6 6. STRAP EMT WITHIN 36" OF BOXES -- NEC 358.30 A 7. SECURE SERVICE BOND TO STRUCTURE 8. SOME CLIPS FOR FIXTURES NOT SECURED TO GRID. 9. MAKE SURE YOU HAVE PROPERLY SIZED EQUIPMENT GROUNDS -- IT APPEARS YOU MAY NOT - NEC 250.122 |
|
12/01/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELLED PER SUPER |