Permit: T05CM05315

Parcel: 10714208A


Addresses:

2480 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM05315

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/11/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/08/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
12/07/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. UP SIDE EQUIPMENT GROUND WHERE REQUIRED BY
NEC 250.122 B
2. LOW VOLTAGE WIRING CORRECTIONS NOT MADE
3. CHECK RACEWAY FILL - NEC CHAPTER 9 TABLE 1
4. FINISH ALL WIRING ABOVE CEILING
12/05/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE OVERFILLED J-BOXES -- NEC 314.16
2. GROUND ALL EQUIPMENT WITH EQUIPMENT GROUNDING CONDUCTOR -- NEC 250.148
3. SEAL RACEWAYS FOR WALKINS -- NEC 300.7
4. SUPPORT WIRES FOR FIXTURES TO BE AT OPPOSITE CORNERS.
5. LOW VOLTAGE WIRING TO BE SUPPORTED BY STRUCTURE AND NOT OTHER EQUIPMENT AND RAN IN A NEAT AND WORKMANLIKE MANNER -- NEC 300.11 B, NEC 800.6
6. STRAP EMT WITHIN 36" OF BOXES -- NEC 358.30 A
7. SECURE SERVICE BOND TO STRUCTURE
8. SOME CLIPS FOR FIXTURES NOT SECURED TO GRID.
9. MAKE SURE YOU HAVE PROPERLY SIZED EQUIPMENT GROUNDS -- IT APPEARS YOU MAY NOT - NEC 250.122
12/01/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELLED PER SUPER