Permit: T05CM05315

Parcel: 10714208A


Addresses:

2480 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T05CM05315

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2007 ELECTRIC - UFER Approved IVRS - Inspection :*
12/11/2006 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
1) PROVIDE APPROVAL LETTER FROM ENGINEER CONCERNING DELETION OF UFER
2) ROUTE NEUTRAL TO EACH SERVICE DISCONNECT AND BOND TO ENCLOSURE-NEC 250.24B
3) NEED TO POST BOND FOR POWER
4) MAKE SURE YOU LOCK OUT ANY OPEN WIRING THAT MAY BECOME ENERGIZED