Permit: T05CM05315
Permit Details
Apply Date:
10/18/2005
Applicant:
SAKELLAR, C NICHOLAS
Description:
C OF O FOR RESTAURANT ONLY
Architects:
- SAKELLAR, C NICHOLAS
Contractors:
- FARWEST DEVELOPMENT AND CONSTRUCTION OF THE SOUT
Permit Reviews
Permit Number - T05CM05315
Permit Status: C of o
Permit Description: C OF O FOR RESTAURANT ONLY
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/12/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 01/13/2007 | COMPLETED |
01/13/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 04/10/2007 | COMPLETED |
02/10/2006 | POST 3RD PARTY REVIEW | 03/23/2006 | COMPLETED |
04/12/2006 | RESUBMITTAL | 05/24/2006 | COMPLETED |
10/18/2005 | PLANS OK TO SUBMIT - 3RD PARTY | 10/20/2005 | COMPLETED |
10/20/2005 | 3RD PARTY REVIEW-COMMERCIAL | 02/10/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM05315
Permit Status: C of o
Permit Description: C OF O FOR RESTAURANT ONLY
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/18/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T05CM05315
Permit Description: C OF O FOR RESTAURANT ONLY
Total Completed Inspections - 50
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2006 | ELECTRIC - TEMPORARY SERVICE | CCLEMENS | Approved | IVRS - Inspection :* |
07/10/2006 | ELECTRIC - CONSTRUCTION POWER | RMAJUTA | Approved | IVRS - Inspection :* |
07/25/2006 | SITE - SEWER | RMYERS | Approved | IVRS - Inspection :* |
08/22/2006 | REINFORCED MASONRY PRE-GROUT | AQUIROZ | Approved | IVRS - Inspection :* TOP OUT MAIN BUILDING |
09/18/2006 | ROOF NAILING | AQUIROZ | Approved | IVRS - Inspection :* EXCLUDES NORTHEAST ROOM |
09/18/2006 | EXT METAL CLIPS/EXT SHEATHING | AQUIROZ | Approved | IVRS - Inspection :* |
09/21/2006 | BUILDING PRE-SLAB | AQUIROZ | Approved | IVRS - Inspection :* FROM COLUMNS TO COLUMNS ONLY |
10/04/2006 | PLUMBING - ROOF DRAINS | RMYERS | Approved | IVRS - Inspection :* |
10/16/2006 | PLUMBING - YARD WTR LINE/TEST | RMYERS | Approved | IVRS - Inspection :* |
10/19/2006 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
10/25/2006 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :* PARTIAL OK HARD CEILINGS RMS. 117, 116, 115, 103, 106 |
10/26/2006 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | IVRS - Inspection :* TYPE 1 HOODS NON-COMBUSTIBLES WALL AT REAR RESTROOM LIDS, OK TO COVER DRY STORAGE OK TO WRAP 10X10 & 12 EX. DUCT |
10/26/2006 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* |
10/27/2006 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* |
11/02/2006 | MECHANICAL - PROGRESS | CWILLIAM | Approved | IVRS - Inspection :* 1) TYPE I EXHAUST HOOD 16 GA. BLK IRON DUCTS 2) OK TO WRAP 3 M INSUL. 3) NOTE: CONTINUE WRAP UP INTO TOP OF CURB, NOT JUST TO WOOD/SHEATHING |
11/08/2006 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | Visual only - no presure test |
11/13/2006 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection :* 1. IT APPEARS THAT YOU HAVE MODIFIED THE PLUMBING IN A COUPLE OF PLACES. NO REDLINES ON SITE NO REVISED APPROVED PLAN REVISION. 2. N/H BANDS NOT APPROVED FOR ABS. 3. NO TEST ON MODIFIED PLUMBING. 4. HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP TRAP ARM MAY ONLY CHANGE DIRECTION 90 DEG. 5. PLUMBER TO CAP OFF ALL OPEN PIPING ASAP!! |
11/14/2006 | PLUMBING - BACK WATER VALVE | RMYERS | Approved | IVRS - Inspection :* |
11/14/2006 | PLUMBING - SEWER HCS CONNECT | RMYERS | Approved | IVRS - Inspection :* |
11/14/2006 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* |
11/15/2006 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* INSTALL GLASS FIBER INSULATION WITH ASJ (LIKE THE REST) ON HOT WATER SYSTEM. |
11/22/2006 | EXCAVATION/LAYOUT REBAR & ZON | GDABBS | Approved | IVRS - Inspection :* TWO LIGHT POLE BASES |
11/22/2006 | ELECTRIC - UNDERGROUND | CCLEMENS | Approved | IVRS - Inspection :* 1) INSPECTION FOR EXTERIOR PARKING AREA POLES 2) RACEWAYS DO NOT HAVE PROPER BURIAL DEPTH-NEC 300.5 24" MAKE SURE IN PARKING AREAS 3) PROVIDE LETTER FROM ARCHITECT CONCERNING DELETION OF POLES 4) OK COVER 2 CENTER AREA POLES |
11/22/2006 | ELECTRIC - OUTDOOR LIGHTING | CCLEMENS | Approved | IVRS - Inspection :* |
12/01/2006 | MECHANICAL - ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* EXCLUDES DINING AREA |
12/08/2006 | STEM WALL/RETAINING WALL | AALEGRIA | Approved | IVRS - Inspection :* PARTIAL @ DUMPSTER ENCLOSURE |
12/11/2006 | ELECTRIC - UFER | CCLEMENS | Approved | IVRS - Inspection :* 1) PROVIDE APPROVAL LETTER FROM ENGINEER CONCERNING DELETION OF UFER 2) ROUTE NEUTRAL TO EACH SERVICE DISCONNECT AND BOND TO ENCLOSURE-NEC 250.24B 3) NEED TO POST BOND FOR POWER 4) MAKE SURE YOU LOCK OUT ANY OPEN WIRING THAT MAY BECOME ENERGIZED |
12/11/2006 | ELECTRIC - TEMP POWER FOR TEST | CCLEMENS | Approved | IVRS - Inspection :* |
12/11/2006 | ELECTRIC - CABLE DROP | CCLEMENS | Approved | IVRS - Inspection :* |
12/11/2006 | ELECTRIC - ABOVE CEILING | CCLEMENS | Approved | IVRS - Inspection :* |
12/22/2006 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* OK FOR GAS CLEARANCE SCHEDULE FINAL AFTER POWER IS ON |
12/22/2006 | U VALUE FOR WINDOW | AQUIROZ | Approved | IVRS - Inspection :* |
12/22/2006 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
01/09/2007 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL |
01/09/2007 | NPPO - FINAL | ACONNOR | Approved | |
01/09/2007 | LANDSCAPE - FINAL | ACONNOR | Approved | |
01/11/2007 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
01/11/2007 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
01/16/2007 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection :* |
01/16/2007 | OUTDOOR LIGHTING FINAL | CCLEMENS | Approved | IVRS - Inspection :* |
01/18/2007 | ENGINEERING - FINAL | MRUSSO | Approved | |
01/19/2007 | PLUMBING - GAS PRESS TEST FNL | RMYERS | Approved | IVRS - Inspection :* |
01/25/2007 | STUCCO MESH | JBURGE | Approved | IVRS - Inspection :* |
01/26/2007 | FIRE - KITCHEN EXH HOOD FINAL | LLAKEY | Approved | |
01/26/2007 | FIRE - FINAL | LLAKEY | Approved | |
01/29/2007 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* OK C OF O |
01/31/2007 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* CORRECTIONS MADE OK OK FOR C OF O S.T.O.I |
01/31/2007 | HEALTH DEPT - FINAL 724-7908 | JTERREL | Approved | PER HEALTH INSP |
04/03/2007 | MECHANICAL - HOODS | JMILITEL | Approved | JOB CARD |
04/03/2007 | SIGN - FINAL | DCAPPLE | Approved | ISSUE THE C OF O FOR ONLY THE PORTION OF THE SITE THE RESTAURANT IS ON. MAKE SURE THE C OF O SPECIFIES THAT IT IS ONLY FOR THAT PORTION OF THE SITE THAT THE RESTAURANT IS ON. |