Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address NEW:
2221 N ROSEMONT BL
Apply Date:
02/23/2000
Applicant:
BEACH, RICHARD A
Description:
NEW NURSING HOME:TEMP C/O FOR ADMIN OFFICES, BUILDING A ,B,C & A-SOUTH
Architects:
  • BEACH, RICHARD A
Contractors:
  • TL ROOF AND ASSOCIATES

Permit Reviews

Permit Number - T00CM00852
Permit Status: C of o
Permit Description: NEW NURSING HOME:TEMP C/O FOR ADMIN OFFICES, BUILDING A ,B,C & A-SOUTH
Start Date Submittal Complete Date Status  
07/14/2000 3RD PARTY REVIEW-COMMERCIAL 11/30/2000 COMPLETED Review Details
07/18/2002 SITE 07/18/2002 COMPLETED Review Details
11/30/2000 REVISION 04/02/2001 COMPLETED Review Details

Completed Inspections

Permit Status: C of o
Permit Number: T00CM00852
Permit Description: NEW NURSING HOME:TEMP C/O FOR ADMIN OFFICES, BUILDING A ,B,C & A-SOUTH
Total Completed Inspections - 53
Date Description Inspector Results Comments
10/31/2000 STEM WALL/RETAINING WALL AMATHIES Approved
11/03/2000 BUILDING PRE-SLAB AMATHIES Approved
11/27/2000 REINFORCED MASONRY PRE-GROUT EMONAHAN Approved 6 LIFT EAST SIDE
12/14/2000 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection 0000*
OK WALLS BLD "A"
12/18/2000 PLUMBING - INTERMEDIATE TRINIVJR Approved IVRS - Inspection 0000*
RAIN LEADER WATER TEST OK
ALL CORRECTIONS HAVE BEEN MADE
OK FOR DRYWALL
NOTE: 1 RAIN LEADER ON WEST SIDE LOST ITS TEST
12/19/2000 SHEET ROCK NAILING AMATHIES Approved IVRS - Inspection 0000*
12/20/2000 PLUMBING - ROUGH, SOIL TRINIVJR Approved IVRS - Inspection 0000*
SOIL WATER TEST OK
THIS INSPECTION IS FOR SOUTH WING OF BLDG B MAIN TRUNK LINE ONLY
OK TO BACKFILL TRENCH
12/20/2000 EXCAVATION/LAYOUT REBAR & ZON AMATHIES Approved IVRS - Inspection 0000*
12/26/2000 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection 0000*
OK BUILDING "C" MAIN ENTRY
12/28/2000 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection 0000*
OK BLD 'B' SOUTH EAST UNDERGROUND
01/03/2001 ELECTRIC - UFER DSANTACR Approved IVRS - Inspection 0000*
01/22/2001 FIRE - ALARM FINAL FIRE Approved
01/22/2001 FIRE SPKLR - FINAL Fire Approved
01/22/2001 FIRE SPKLR - FINAL FIRE Approved
01/22/2001 FIRE SPKLR - OH PIPING & HYDRO FIRE Approved
01/22/2001 FIRE SPKLR - OH PIPING & HYDRO FIRE Approved
01/24/2001 SIGN - FINAL JYBARRA Approved IVRS - Inspection 0000*
01/24/2001 HEALTH DEPT - FINAL 724-7908 HEALTH Approved
09/14/2001 PLUMBING - TEMP POWER FOR TEST JSTANLEY Approved
09/25/2001 FRAMING AMATHIES Approved IVRS - Inspection 0000*
09/26/2001 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection 0000*PARTIAL OK TO COVER HARD LID BLDG B 205 3. 1.) WRAP COPPER REF. BUNDLE TO ISOLATE FROM STEEL CLEVIS HANGERS 2.) NEED TO ACCESS PANELS AT COMB. FIRE DAMPERS.
10/03/2001 BOILER FINAL RLOHRMAN Approved IVRS - Inspection 0000*NO BOILER INSTALLED PARTIAL
10/11/2001 PLUMBING - GAS PRESSURE TEST TRINIVJR Approved IVRS - Inspection 0999*1.) WILL REQUIRE A APPROVED DRANING OF LOCATION AND BTU RATING FOR BACKUP GENERATOR. SHOWING LENGTH OF GAS RUN AND CFH RATEING PRIOR TO INSPECTION.
10/25/2001 BUILDING ABOVE CEILING AMATHIES Approved IVRS - Inspection 0000*
11/08/2001 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection 0000*ALL A/H I.D.
11/19/2001 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection 0000*PROVIDE VIBRATION ISOLATORS UNDER CONDENSING UNITS AS PER SPECS. PERMANENTLY LABEL EQUIPMENT ON ROOF. OK FOR TEMP C OF O.
11/19/2001 ENGINEERING - FINAL DROBERTS Approved TEMPORARY C OF O APPROVED, FINAL GRADING #9190 FOR THIS SITE REQUIRED PRIOR TO THE RELEASE OF THE FINAL C OF O
11/20/2001 MEDICAL - GAS/TEST INTERMED JMILITEL Approved IVRS - Inspection 0000*NO NEED GAS IN BLGD A OK FOR TEMP C OF O.
11/20/2001 PLUMBING - FINAL TRINIVJR Approved IVRS - Inspection 0000*1.) PLBG. TEMP C OF O. IS OK FOR BLDG. A ONLY.
11/20/2001 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection 0000*BUILDING "A" ONLY TEMP C OF O APPROVED.
11/23/2001 NPPO - FINAL LANDSCAP Approved
11/23/2001 LANDSCAPE - FINAL PGILBERT Approved NEED AN APPROVED COPY OF SITE AND LANDSCAPE PLANS ON SITE.
11/23/2001 U VALUE FOR WINDOW AMATHIES Approved IVRS - Inspection 0000*
12/11/2001 BUILDING - FINAL AMATHIES Approved IVRS - Inspection 0000*
08/08/2002 MECHANICAL - PROGRESS JMILITEL Approved
08/08/2002 MECHANICAL - HOODS JMILITEL Approved
08/08/2002 ELECTRIC - TEMP POWER FOR TEST DSANTACR Approved
08/09/2002 MECHANICAL - TEMP PWR FOR TEST JMILITEL Approved
08/09/2002 BUILDING - TEMP POWER FOR TEST AQUIROZ Approved
08/09/2002 STUCCO MESH AQUIROZ Approved IVRS - Inspection 0000*
08/09/2002 ROOF NAILING AQUIROZ Approved IVRS - Inspection 0000*
08/09/2002 EXT METAL CLIPS/EXT SHEATHING AQUIROZ Approved IVRS - Inspection 0000*
10/09/2002 RIGHT OF WAY - FINAL PWHIDDON Approved
10/10/2002 FIRE - FINAL LTHOMAS Approved
10/10/2002 FIRE - LANE SIGNS LTHOMAS Approved
10/10/2002 FIRE - HYDRANTS LTHOMAS Approved OK FOR C OF O
10/10/2002 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
10/10/2002 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
10/10/2002 PLUMBING - PROGRESS TRINIVJR Approved
10/10/2002 PLUMBING - SEWER HCS CONNECT TRINIVJR Approved
10/10/2002 PLUMBING - YARD WTR LINE/TEST TRINIVJR Approved
10/10/2002 PLUMBING - ABOVE CEILING TRINIVJR Approved
11/07/2002 ELECTRIC - SERVICE RELOCATION DSANTACR Approved