Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 04/04/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000*1.) GAS PRESSURE TEST OF 60LBS IS OK 2.) OVERHEAD GAS SYSTEMS IS OK FOR BLDG . C NORTH. |
| 03/28/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Partial Approval |
PER TRINI. |
| 10/11/2001 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
IVRS - Inspection 0999*1.) WILL REQUIRE A APPROVED DRANING OF LOCATION AND BTU RATING FOR BACKUP GENERATOR. SHOWING LENGTH OF GAS RUN AND CFH RATEING PRIOR TO INSPECTION. |
| 10/10/2001 |
PLUMBING - GAS PRESSURE TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000* |