Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T00CM00852
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2002 | MECHANICAL - INTERMEDIATE | Approved | ||
| 06/24/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) PROVIDE SCREW | |
| 06/21/2002 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
| 06/06/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK FOR SHEET ROCK BLDG. A 2ND FLOOR ROOMS 205, 206, 207,208,212,218. | |
| 05/24/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*BLDG C SOUTH OK TO COVER AREA WITH GRID TO DATE. | |
| 05/02/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK FOR SHEET ROCK BLDG 1 ROOM 106,107,108,109,116. BE SURE TO INSULATE CONDENSATE PIPE PRIOR TO SHEETROCK. NEED TO SEE LISTING ON CEILING DAMPERS. | |
| 04/17/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK FOR SHEET ROCK BLDG. C NORTH STILL NEED TO SEE LOBBY AREA. | |
| 04/15/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* NEED TO SEEE HEAVIER ANGLE ON FIRE DAMPERS. BE SURE TO MAINTAIN CLEAR ACCESS FOR FILTERS & SERVICE PANELS. CHECKED DAMPER OPENING BLDG. A SOUTH WING. | |
| 04/05/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK FOR SHEET ROCK IN LOCKER ROOMS BLDG. C SOUTH OK FOR SHEET ROCK IN DISH WASH AREA. | |
| 04/03/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*INSPECTED FIRE DAMPER OPENINGS BLDG C. SOUTH & NORTH OK TO INSTALL DAMPERS & ANGELS. RECALL WHEN COMPLETELY INSTALLED. | |
| 04/02/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*NEED TO SEE FIRE DAMPER OPENINGS. OK FOR PARTIALSHEET ROCK ROOMS 173,174,170,169,169.1,160,162,162,1,159. | |
| 09/26/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*PARTIAL OK TO COVER HARD LID BLDG B 205 3. 1.) WRAP COPPER REF. BUNDLE TO ISOLATE FROM STEEL CLEVIS HANGERS 2.) NEED TO ACCESS PANELS AT COMB. FIRE DAMPERS. | |
| 09/13/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TO SHEETROCK BLDG A ROOMS 233,235,231,239. | |
| 09/07/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TO SHEET ROCK 2ND FLOOR STAIRWELL NORTH SIDE BLDG. A, ROOM 221,220,222,223, | |
| 08/22/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK FOR SHEETROCK BLDG A 2ND FLOOR ROOMS 261, 258, INSULATE CONDENSATE DRAIN 252, 251, 249,250, CHECKED FIRE DAMPER OPENINGS IN MIDDLE AREA 2ND FLOOR. | |
| 08/16/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TO INSTALL DAMPERS IN S.W. WING 1ST FLOOR A OK TO SHEET ROCK IN SW WIRING 1ST FLOOR BLDG A SEAL ALL OPENING THRU FIRE WALLS. OK TO SHEETROCK RMS 264,263,267,268, 2ND FLOOR BLDG. A. | |
| 08/13/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*FRAME OPENINGS FOR FIRE DAMPERS BLDG A 1ST FLOOR CORRECT & RECALL FOR INSPECTIONS. | |
| 08/09/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 08/02/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*PROVIDE ACCESS & ELECTRICAL TO FIRE SMOKE DAMPER IN DURING BLDG. A PROVIDE ACCESS FOR SERVICE ON FAN COIL N.E. AND OF BLDG A UNIT NOT LEVEL. OK TO SHEETROCK DINING AREA. | |
| 07/18/2001 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) FIRE SMOKE DAMPER NOT WIRED 2.) FIRE CAULK PENETRATION THRU FIRE WALLS 3.) PROVIDE A SECONDARY DRAIN ON AIR HANDLER OK TO SHEETROCK B231,232,223,233 | |
| 06/28/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*O.K. TO SHEET ROCK 205,204,207,206,214,216,BLDG B. 222 | |
| 06/25/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*O.K. TO SHEET ROCK 218,220,217,219 BLDG B | |
| 06/20/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*CH. ALL COPPER REF. LINE BUNDLES.PASSING STEEL-STEEL HOUSING,ETC. RMS.224-230-225-229-226-228.2ND FLOOR BUILDING B. |
|
| 06/18/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TO SHEETROCK B238,B237,B239,B245,B246,B247. | |
| 06/14/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*2ND FLOOR INSPECTION-OK TO SHEET ROCK ROOMS B249,B252,B250,B251 | |
| 06/11/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TO COVER CEILINGS IN LOBBY. | |
| 06/08/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*USE FIRE CAULK AROUND FIRE DAMPER OPENING IN LOBBY.PROVIDE AN ACCESS PANEL FOR AIR HANDLER IN LOBBY.WILL CLEAR TO COVER AFTER HOLES THRU FIRE WALL ARE SEALED ANDF OPENINGS FRAMED. | |
| 05/29/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TO SHEET ROCK B116,B139,B129,B130,B127,B125 | |
| 05/24/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*SOUTH END CORNER AS NOTED BY J.M. 5/17/01.OK TO COVER HARD CEILINGS.BE SURE TO MAINTAIN PROPER ACCESS TO ALL AIR HANDLERS.RM-B-159-OK TO COVER LID. | |
| 05/17/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TO COVER B105,106,107,108,117,118,119,120.LEAVE BATHROOM CEILINGS OPEN UNTIL EXHAUST DUCT IS INSPECTED. | |
| 05/15/2001 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* NOT READY | |
| 05/04/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) OK TO SHEET ROCK ROOMS 156, 155, 146, 148, 145, 147, 162, 163, 157, 158. LEAVE OUT BATHROOM CEILINGS IN ROOMS 147 & 145 UNTIL MECH IS DONE |
|
| 05/02/2001 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* NOT READY | |
| 05/01/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK TO SHEET ROCK NORTH END OF BLDG B | |
| 04/16/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* CARRIER AIR HANDLERS SECONDARY DRAIN MUST BE PIPED TO AN AREA WHERE IT CAN BE VISABLY OBSERVED |