Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T00CM00852

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2002 MECHANICAL - INTERMEDIATE Approved
06/24/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) PROVIDE SCREW
06/21/2002 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
06/06/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK FOR SHEET ROCK BLDG. A 2ND FLOOR ROOMS 205, 206, 207,208,212,218.
05/24/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*BLDG C SOUTH OK TO COVER AREA WITH GRID TO DATE.
05/02/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK FOR SHEET ROCK BLDG 1 ROOM 106,107,108,109,116. BE SURE TO INSULATE CONDENSATE PIPE PRIOR TO SHEETROCK. NEED TO SEE LISTING ON CEILING DAMPERS.
04/17/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK FOR SHEET ROCK BLDG. C NORTH STILL NEED TO SEE LOBBY AREA.
04/15/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000* NEED TO SEEE HEAVIER ANGLE ON FIRE DAMPERS. BE SURE TO MAINTAIN CLEAR ACCESS FOR FILTERS & SERVICE PANELS. CHECKED DAMPER OPENING BLDG. A SOUTH WING.
04/05/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK FOR SHEET ROCK IN LOCKER ROOMS BLDG. C SOUTH OK FOR SHEET ROCK IN DISH WASH AREA.
04/03/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*INSPECTED FIRE DAMPER OPENINGS BLDG C. SOUTH & NORTH OK TO INSTALL DAMPERS & ANGELS. RECALL WHEN COMPLETELY INSTALLED.
04/02/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*NEED TO SEE FIRE DAMPER OPENINGS. OK FOR PARTIALSHEET ROCK ROOMS 173,174,170,169,169.1,160,162,162,1,159.
09/26/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*PARTIAL OK TO COVER HARD LID BLDG B 205 3. 1.) WRAP COPPER REF. BUNDLE TO ISOLATE FROM STEEL CLEVIS HANGERS 2.) NEED TO ACCESS PANELS AT COMB. FIRE DAMPERS.
09/13/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TO SHEETROCK BLDG A ROOMS 233,235,231,239.
09/07/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TO SHEET ROCK 2ND FLOOR STAIRWELL NORTH SIDE BLDG. A, ROOM 221,220,222,223,
08/22/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK FOR SHEETROCK BLDG A 2ND FLOOR ROOMS 261, 258, INSULATE CONDENSATE DRAIN 252, 251, 249,250, CHECKED FIRE DAMPER OPENINGS IN MIDDLE AREA 2ND FLOOR.
08/16/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TO INSTALL DAMPERS IN S.W. WING 1ST FLOOR A OK TO SHEET ROCK IN SW WIRING 1ST FLOOR BLDG A SEAL ALL OPENING THRU FIRE WALLS. OK TO SHEETROCK RMS 264,263,267,268, 2ND FLOOR BLDG. A.
08/13/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*FRAME OPENINGS FOR FIRE DAMPERS BLDG A 1ST FLOOR CORRECT & RECALL FOR INSPECTIONS.
08/09/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
08/02/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*PROVIDE ACCESS & ELECTRICAL TO FIRE SMOKE DAMPER IN DURING BLDG. A PROVIDE ACCESS FOR SERVICE ON FAN COIL N.E. AND OF BLDG A UNIT NOT LEVEL. OK TO SHEETROCK DINING AREA.
07/18/2001 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*1.) FIRE SMOKE DAMPER NOT WIRED 2.) FIRE CAULK PENETRATION THRU FIRE WALLS 3.) PROVIDE A SECONDARY DRAIN ON AIR HANDLER OK TO SHEETROCK B231,232,223,233
06/28/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*O.K. TO SHEET ROCK 205,204,207,206,214,216,BLDG B. 222
06/25/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*O.K. TO SHEET ROCK 218,220,217,219 BLDG B
06/20/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*CH. ALL COPPER REF. LINE
BUNDLES.PASSING STEEL-STEEL HOUSING,ETC.
RMS.224-230-225-229-226-228.2ND FLOOR BUILDING B.
06/18/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TO SHEETROCK B238,B237,B239,B245,B246,B247.
06/14/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*2ND FLOOR INSPECTION-OK TO SHEET ROCK ROOMS B249,B252,B250,B251
06/11/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TO COVER CEILINGS IN LOBBY.
06/08/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*USE FIRE CAULK AROUND FIRE DAMPER OPENING IN LOBBY.PROVIDE AN ACCESS PANEL FOR AIR HANDLER IN LOBBY.WILL CLEAR TO COVER AFTER HOLES THRU FIRE WALL ARE SEALED ANDF OPENINGS FRAMED.
05/29/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TO SHEET ROCK B116,B139,B129,B130,B127,B125
05/24/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*SOUTH END CORNER AS NOTED BY J.M. 5/17/01.OK TO COVER HARD CEILINGS.BE SURE TO MAINTAIN PROPER ACCESS TO ALL AIR HANDLERS.RM-B-159-OK TO COVER LID.
05/17/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TO COVER B105,106,107,108,117,118,119,120.LEAVE BATHROOM CEILINGS OPEN UNTIL EXHAUST DUCT IS INSPECTED.
05/15/2001 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000* NOT READY
05/04/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000* 1) OK TO SHEET ROCK ROOMS
156, 155, 146, 148, 145, 147, 162, 163, 157, 158.
LEAVE OUT BATHROOM CEILINGS IN ROOMS 147 & 145 UNTIL MECH IS DONE
05/02/2001 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000* NOT READY
05/01/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK TO SHEET ROCK NORTH END OF BLDG B
04/16/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000* CARRIER AIR HANDLERS SECONDARY DRAIN MUST BE PIPED TO AN AREA WHERE IT CAN BE VISABLY OBSERVED