Permit: T00CM00852

Parcel: 12109290B


Addresses:

2221 N ROSEMONT BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T00CM00852

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O.
08/02/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) PROVIDE SECONDARY DRAIN ON AIR HANDLERS 2.) LABEL EQUIPMENT. 3.) PROVIDE ELEC. DISCONNECT AIR HANDLER EAST HALL. 4.) DUCT NOT HOOKED. UP NURSE STATION. 5. WALK ALL UNITS & CHECK FOR VIOLATION.
07/10/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000* OK FOR C OF O BLDG. C.
07/01/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000* REMOVE SCREWS FROM DRYER VENTS & SUPPORT VENT PIPE AS NEEDED. PROVIDE SCREWS IN BOILER VENT CONNECTOR SEAL OPENING THRU CEILING. PROVIDE ACCESS TO DUCT SMOKE DETECTOR IN KITCHEN & MAIN ENTRY. SMOKE DETECTOR ARE OK ROOF TOP EQUIPMENT IS OK. OK FOR TEMP C OF O. BLDG. C.
06/28/2002 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*
06/24/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) PROVIDE SCREWS IN VENT CONNECTOR TO BOILER & PIZZA OVEN BLDG C. 2) NEED TO SEE DUCT SMOKE DETECTOR BLDG C. 3.) NEED TO SEE FUSES IN AC UNITS RELOCATE OUTSIDE AIR AC C-6.
06/21/2002 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/19/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*PROVIDE VIBRATION ISOLATORS UNDER CONDENSING UNITS AS PER SPECS. PERMANENTLY LABEL EQUIPMENT ON ROOF. OK FOR TEMP C OF O.
08/30/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*BLDG. B OK.
01/23/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
OK FOR TEMP C OF O NORTH END OF BLDG C
01/22/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
INSTALL THREADED PLUG AN SECONDARY DRAIN OUTLET ON AIR HANDLER
INSTALL CONDENSATE DRAINS TO A/C UNIT ON ROOF
MARK DATA PLATE W/PROPER HEAT STRIP AND FUSE UNIT ACCORDINGLY
HOOK UP LOW VOLTAGE
FINISH PIPING CONDENSOR ON ROOF
NEED PERMANENT LADDER TO UPPER ROOF
LABEL A/C EQUIPMENT
INSTALL OUTSIDE AIR VENT ON PACKAGE UNIT