Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00CM00852
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*OK FOR C OF O. | |
| 08/02/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) PROVIDE SECONDARY DRAIN ON AIR HANDLERS 2.) LABEL EQUIPMENT. 3.) PROVIDE ELEC. DISCONNECT AIR HANDLER EAST HALL. 4.) DUCT NOT HOOKED. UP NURSE STATION. 5. WALK ALL UNITS & CHECK FOR VIOLATION. | |
| 07/10/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* OK FOR C OF O BLDG. C. | |
| 07/01/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* REMOVE SCREWS FROM DRYER VENTS & SUPPORT VENT PIPE AS NEEDED. PROVIDE SCREWS IN BOILER VENT CONNECTOR SEAL OPENING THRU CEILING. PROVIDE ACCESS TO DUCT SMOKE DETECTOR IN KITCHEN & MAIN ENTRY. SMOKE DETECTOR ARE OK ROOF TOP EQUIPMENT IS OK. OK FOR TEMP C OF O. BLDG. C. | |
| 06/28/2002 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 06/24/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PROVIDE SCREWS IN VENT CONNECTOR TO BOILER & PIZZA OVEN BLDG C. 2) NEED TO SEE DUCT SMOKE DETECTOR BLDG C. 3.) NEED TO SEE FUSES IN AC UNITS RELOCATE OUTSIDE AIR AC C-6. | |
| 06/21/2002 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 11/19/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*PROVIDE VIBRATION ISOLATORS UNDER CONDENSING UNITS AS PER SPECS. PERMANENTLY LABEL EQUIPMENT ON ROOF. OK FOR TEMP C OF O. | |
| 08/30/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*BLDG. B OK. | |
| 01/23/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* OK FOR TEMP C OF O NORTH END OF BLDG C |
|
| 01/22/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* INSTALL THREADED PLUG AN SECONDARY DRAIN OUTLET ON AIR HANDLER INSTALL CONDENSATE DRAINS TO A/C UNIT ON ROOF MARK DATA PLATE W/PROPER HEAT STRIP AND FUSE UNIT ACCORDINGLY HOOK UP LOW VOLTAGE FINISH PIPING CONDENSOR ON ROOF NEED PERMANENT LADDER TO UPPER ROOF LABEL A/C EQUIPMENT INSTALL OUTSIDE AIR VENT ON PACKAGE UNIT |