Permit: T00CM00852

Parcel: 12109290B


Addresses:

2221 N ROSEMONT BL


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T00CM00852

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
10/10/2002 PLUMBING - YARD WTR LINE/TEST Approved
03/22/2002 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*1.) 4" WATER LINE TESTED LAST 150' TO BLDG. 2.) 50# AIR TEST OK OK TO COVER. 3.) ROOF DRAINS SOUTH "C" OK WATER TEST OK OK TO COVER.
03/19/2002 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*1.) 4" WATER SERVICE @ WEST SIDE IS OK TO BACKFILL.
08/24/2001 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*
07/30/2001 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*1.) (2) 2" BACKFLOW PREVENTERS @ METER LOCATION ARE OK 2.) P.O.C. OF NEW 4" WATER SERVICE TO EXSISTING WATER LINE IS OK 3.) OK TO BACKFILL TRENCH.
07/05/2001 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*1.) BACKFLOW PREVENTERS @ SOUTH SIDE OF PROJECT ARE OK 2.) OK TO BACKFILL TRENCH
07/02/2001 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*1.) 4" WATER MAIN HAS LEAK WHERE 2 " CONNECTS INTO 4" 2.) OK TO BACKFILL TRENCH UP TO POINT WHERE 4" GOES EAST 3.) DO NOT COVER AREA WHERE LEAK IS RECALL FOR INSPECTION WHEN REPAIR HAS BEEN MADE 4.) 4" MAIN IS MISSING ONE MEGA LUG KIT.
06/28/2001 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection 0000*1.) NOT READY FOR INSPECTIONS
04/30/2001 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection 0000* ?
02/20/2001 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000* 1) THIS INSP WAS FOR NEW 4" MAIN RELOCATED AROUND BLDG. 2) MUST SEE FINAL CONNECTION AT EXSISTING WATER MAIN AND AT BACKFLOW PREVENTOR 3) OK TO BACKFILL TRENCH 5) NOTE: WILL REQUIRE REVISED AND APPROVED DRAWING ON NEW 4" WATER MAIN BEFORE FINAL INSP.