Permit Details

Status:
Complete
Type:
Commercial Building
Address NEW:
6950 S COUNTRY CLUB RD
Apply Date:
05/09/2025
Applicant:
Andrew Christopher
Description:
Manufacturing floor tenant improvement (NOTE: C of O cannot be issued until the RTO2 mechanical equipment is installed and passed inspection via a separate permit.)

Permit Reviews

Permit Number - TC-COM-0525-00955
Permit Status: Complete
Permit Description: Manufacturing floor tenant improvement (NOTE: C of O cannot be issued until the RTO2 mechanical equipment is installed and passed inspection via a separate permit.)
Start Date Submittal Complete Date Status  
07/03/2025 COMMERCIAL REVIEW - FULL v.2 07/29/2025 REQUIRES RESUBMIT Review Details
08/20/2025 COMMERCIAL REVIEW - FULL v.4 08/25/2025 APPROVED Review Details
01/14/2026 BUILDING DEFERRED SUBMITTAL REVIEW v.1 01/20/2026 REQUIRES RESUBMIT Review Details
01/08/2026 BUILDING DEFERRED SUBMITTAL REVIEW v.1 01/12/2026 APPROVED Review Details
12/09/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.2 12/12/2025 APPROVED Review Details
08/01/2025 COMMERCIAL REVIEW - FULL v.3 08/19/2025 REQUIRES RESUBMIT Review Details
04/21/2026 BUILDING DEFERRED SUBMITTAL REVIEW v.2 04/22/2026 APPROVED Review Details
05/14/2025 COMMERCIAL REVIEW - FULL v.1 06/10/2025 REQUIRES RESUBMIT Review Details
08/25/2025 RESTAMP - COMMERCIAL v.1 08/27/2025 APPROVED Review Details
12/08/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 12/09/2025 REQUIRES RESUBMIT Review Details

Conditions

Permit Number - TC-COM-0525-00955
Permit Status: Complete
Permit Description: Manufacturing floor tenant improvement (NOTE: C of O cannot be issued until the RTO2 mechanical equipment is installed and passed inspection via a separate permit.)
Date Description Comments
05/14/2025 There are two addresses associated with this location 6950 S COUNTRY CLUB RD TUCSON, AZ 85756 & 6950 S COUNTRY CLUB RD UNIT 304 TUCSON, AZ 85756. Please confirm the address for this permit application.
12/04/2025 AIR BALANCING REPORT IS REQUIRED.
12/19/2025 ***NOTE: The RTO2 mechanical equipment on a separate permit must be installed/pass inspection prior to the issuance of the Certificate of Occupancy.
05/14/2025 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.

Outstanding Inspections

Permit Status: Complete
Permit Number: TC-COM-0525-00955
Permite Description: Manufacturing floor tenant improvement (NOTE: C of O cannot be issued until the RTO2 mechanical equipment is installed and passed inspection via a separate permit.)
Total Outstanding Inspections - 9
Last Inspection Date Description Inspector Results Comments
12/04/2025 COT - HCME - Mechanical Intermediate N/A Partial Pass 12-4-25: mechanical intermediate-fix tear to flex at room 117, label junction boxes at column located in front room 117, add seismic wires throughout at room's 115, 116, 117, 118, 119-add tape to flex at connection point of trunk. Reinspection required- schedule when ready.
12/04/2025 COT - HCPL - Plumbing Intermediate N/A Partial Pass 12-4-25: provide hood specifications- upload specs. as an attachment to the city for review.
12/23/2025 BULD - Electrical Clearance N/A Not Applicable 12-23-25: not applicable.
12/04/2025 COT - HCEL - Electrical Above Ceiling N/A Partial Pass 12-4-25: mechanical intermediate-fix tear to flex at room 117, label junction boxes at column located in front room 117, add seismic wires throughout at room's 115, 116, 117, 118, 119-add tape to flex at connection point of trunk. Reinspection required- schedule when ready.
12/04/2025 COT - HCEL - Electrical Intermediate N/A Partial Pass 12-4-25: mechanical intermediate-fix tear to flex at room 117, label junction boxes at column located in front room 117, add seismic wires throughout at room's 115, 116, 117, 118, 119-add tape to flex at connection point of trunk. Reinspection required- schedule when ready.
12/23/2025 COT - HCBU - Building Final N/A Partial Pass 12-23-25: This permitTCCOM 0525-0079 must be completed prior to issuing a Cof O.
12/04/2025 COT - HCPL - Plumbing Above Ceiling N/A Partial Pass 12-4-25: provide hood specifications- upload specs. as an attachment to the city for review.
01/06/2026 COT - HCBU - TCO N/A Partial Pass 1-6-26: okay for a Level 1 TCO.
Pending Fire inspection & see notes from building final.
12/18/2025 COT - FCON - Fire - Final N/A Partial Pass Everything passed just need a knox box and facp sign.

Completed Inspections

Permit Status: Complete
Permit Number: TC-COM-0525-00955
Permit Description: Manufacturing floor tenant improvement (NOTE: C of O cannot be issued until the RTO2 mechanical equipment is installed and passed inspection via a separate permit.)
Total Completed Inspections - 20
Date Description Inspector Results Comments
12/04/2025 COT - HCBU - Building Progress Passed 12-4-25: approved.
12/04/2025 COT - HCBU - Framing Passed 12-4-25: framing at mezzanine approved.
12/04/2025 COT - HCPL - Plumbing Progress Passed 12-4-25: approved.
12/18/2025 COT - FCON - Alarm - Final Passed
12/18/2025 COT - FCON - Sprinkler - Final Passed
12/23/2025 COT - HCME - Mechanical Final Passed 12-23-25: approved.
12/23/2025 COT - HCME - Mechanical Intermediate Passed 12-23-25: approved.
12/23/2025 COT - HCME - Mechanical Progress Passed 12-23-25: approved.
12/23/2025 COT - HCPL - Plumbing Final Passed 12-23-25: approved.
12/23/2025 COT - HCEL - Electrical Progress Passed 12-23-25: approved.
12/23/2025 COT - HCBU - Building Above Ceiling Passed 12-23-25: approved.
12/23/2025 COT - HCPL - Plumbing Intermediate Passed 12-23-25: approved.
12/23/2025 COT - HCEL - Electrical Above Ceiling Passed 12-23-25: approved.
12/23/2025 COT - HCEL - Electrical Final Passed 12-23-25: approved.
12/23/2025 COT - HCEL - Electrical Intermediate Passed 12-23-25: approved.
12/29/2025 ENGR Engineering Final Passed Exterior is complete, all egress doors are uninhibited.
01/05/2026 TRSP - ROW - Final/Close-Out Passed
01/06/2026 COT - HCBU - Building Final Passed 1-6-26: building final approved.
Submit water chlorination report together with elevator certificate to the city for review. Also, address pending condition with regard to installation of RTO-Submit a letter from the architect or engineer of record stating that RTO will be installed on a new unrelated permit.
01/06/2026 COT - HCPL - Plumbing Above Ceiling Passed 1-6-26: approved.
01/08/2026 COT - FCON - Fire - Final Passed