Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 09/17/2025 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
9-17-25: electrical intermediates at room's 107, 108, 109, & 110 verified per plans. Okay to continue construction at progress areas. |
|
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
9-29-25: electrical intermediates at mezzanine verified per plans. Electrical above ceiling at room's 142 approved, 146-add 10 mil tape where copper is making contact with mc cable, 147-fix tear to flex & label junction box, 219-label junction box, 221-label junction box, 220-add knockout to junction box. Okay to proceed with construction at progress areas-Items requiring correction will be verified on re-inspect or at finals. |
| 12/04/2025 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
12-4-25: mechanical intermediate-fix tear to flex at room 117, label junction boxes at column located in front room 117, add seismic wires throughout at room's 115, 116, 117, 118, 119-add tape to flex at connection point of trunk. Reinspection required- schedule when ready. |
| 12/15/2025 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
12-15-25: label all receptacles. |
| 12/23/2025 |
COT - HCEL - Electrical Intermediate |
|
Passed |
12-23-25: approved. |