Permit Number: TC-COM-0525-00955
Parcel: 14042023D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0525-00955
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2025 Commercial Building Standard APPROVED Structural(S) Reviewer (from previous submittal TUC9715001.051525)
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 5/26/2025 5:24:29 PM

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 7/7/2025 1:47:27 PM
07/10/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 7/10/2025 1:11:18 AM
SECOND PLUMBING REVIEW: OK
RESOLVED-1). Plan pages P1.2WH & P4.0WH: what will be drained into laboratory sink? Any harmful discharge will need to
comply with -2018 IPC 302 & 803 **PER RESPONSE COMMENT LAB SINK IS FOR HANDWASHING ONLY**
RESOLVED-2). Plan Page P1.2WH: Missing shut off valve at lift pump. Add shut off valve at lift pump. -2018 IPC 712.2
07/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/29/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: Olga Salazar
PDSD Zoning Review Section

PROJECT: TC-COM-0525-00955– Manufacturing
Tenant Improvement (2nd Review)
6950 S COUNTRY CLUB RD – I-1 Zoning

TRANSMITTAL DATE: July 29, 2025

DUE DATE: July 25th, 2025

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the I-1 zone. Based on the scope of work, add a note specifying the type of manufacturing as General Manufacturing, subject to use specific standards 4.9.5.C.2, .6, .7, & .8 and 4.9.13.Q.

2. COMMENT: Expansion should include the proposed mezzanine horizontal area in the total gross floor area (GFA). Correct the total building area to reflect this increase in GFA.

3. COMMENT: Provide parking calculations based on the new total building area.

4. COMMENT: More comments may be forthcoming based on the next submittal's response.

If you have any questions about this transmittal, please contact Olga.Salazar@tucsonaz.gov.
07/03/2025 PDSD Application Completeness Express REVIEW COMPLETED