Inspection Status: Partial Pass

Inspection History: COT - HCME - Mechanical Progress 

Date Description Inspector Results Comments
COT - HCME - Mechanical Progress  Partial Pass 9-29-25: mechanical intermediates at mezzanine verified per plans. Electrical above ceiling at room's 142 approved, 146-add 10 mil tape where copper is making contact with mc cable, 147-fix tear to flex & label junction box, 219-label junction box, 221-label junction box, 220-add knockout to junction box. Okay to proceed with construction at progress areas-Items requiring correction will be verified on re-inspect or at finals.
12/08/2025 COT - HCME - Mechanical Progress  Partial Pass 12/8/2025 Rooms 115,116,117,118,119 (mezzanine) approved. Okay for ceiling tiles to be placed.
12/15/2025 COT - HCME - Mechanical Progress  Partial Pass 12-15-25: seal penetration above ceiling in rm. 104-seal/add piece of drywall where low voltage at west wall.
12/23/2025 COT - HCME - Mechanical Progress  Passed 12-23-25: approved.