Inspection Status: Partial Pass
Inspection History: COT - HCME - Mechanical Progress
| Date |
Description |
Inspector |
Results |
Comments |
|
COT - HCME - Mechanical Progress |
|
Partial Pass |
9-29-25: mechanical intermediates at mezzanine verified per plans. Electrical above ceiling at room's 142 approved, 146-add 10 mil tape where copper is making contact with mc cable, 147-fix tear to flex & label junction box, 219-label junction box, 221-label junction box, 220-add knockout to junction box. Okay to proceed with construction at progress areas-Items requiring correction will be verified on re-inspect or at finals. |
| 12/08/2025 |
COT - HCME - Mechanical Progress |
|
Partial Pass |
12/8/2025 Rooms 115,116,117,118,119 (mezzanine) approved. Okay for ceiling tiles to be placed. |
| 12/15/2025 |
COT - HCME - Mechanical Progress |
|
Partial Pass |
12-15-25: seal penetration above ceiling in rm. 104-seal/add piece of drywall where low voltage at west wall. |
| 12/23/2025 |
COT - HCME - Mechanical Progress |
|
Passed |
12-23-25: approved. |