Permit: TC-COM-0323-00868
Permit Details
Status:
Issued
Type:
Commercial Building
Address:
5590 E TRAVEL PLAZA WY
Address NEW:
5590 E TRAVEL PLAZA WY
Apply Date:
03/23/2023
Applicant:
Charmalee Jayawardena
Description:
NEW TRUCK TIRE AND LIGHT MECHANICAL MAINTENANCE FACILITY
Permit Reviews
Permit Number - TC-COM-0323-00868
Permit Status: Issued
Permit Description: NEW TRUCK TIRE AND LIGHT MECHANICAL MAINTENANCE FACILITY
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/21/2023 | COMMERCIAL REVIEW - FULL v.2 | 07/21/2023 | REQUIRES RESUBMIT |
| 12/06/2023 | RESTAMP - COMMERCIAL v.1 | 12/07/2023 | APPROVED |
| 06/05/2025 | RESTAMP - COMMERCIAL v.1 | 06/06/2025 | APPROVED |
| 03/26/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 04/01/2025 | APPROVED |
| 07/29/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 08/01/2025 | APPROVED |
| 11/27/2023 | COMMERCIAL REVIEW - FULL v.3 | 12/06/2023 | APPROVED |
| 11/20/2025 | COMMERCIAL REVIEW - FULL v.3 | 12/12/2025 | APPROVED |
| 08/12/2026 | RESTAMP - COMMERCIAL v.1 | 08/18/2026 | APPROVED |
| 05/01/2025 | COMMERCIAL REVIEW - FULL REVISION v.1 | 05/23/2025 | REQUIRES RESUBMIT |
| 03/24/2023 | COMMERCIAL REVIEW - FULL v.1 | 04/21/2023 | REQUIRES RESUBMIT |
| 09/29/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 09/29/2025 | REQUIRES RESUBMIT |
| 07/24/2023 | COMMERCIAL REVIEW - FULL v.1 | 08/16/2023 | REQUIRES RESUBMIT |
| 09/25/2025 | COMMERCIAL REVIEW - FULL v.2 | 09/26/2025 | REQUIRES RESUBMIT |
| 06/05/2025 | COMMERCIAL REVIEW - FULL REVISION v.2 | 06/05/2025 | APPROVED |
| 10/31/2023 | COMMERCIAL REVIEW - FULL v.2 | 11/22/2023 | REQUIRES RESUBMIT |
| 08/07/2025 | COMMERCIAL REVIEW - FULL v.1 | 08/27/2025 | REQUIRES RESUBMIT |
Outstanding Activity Conditions
Permit Number - TC-COM-0323-00868
Permit Status: Issued
Permit Description: NEW TRUCK TIRE AND LIGHT MECHANICAL MAINTENANCE FACILITY
Total Outstanding Activity Conditions - 6
| Date | Name |
|---|---|
| 11/13/2023 | AIR BALANCING/COMMISSIONING REPORT IS REQUIRED. |
| 11/13/2023 | SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED. |
| 11/13/2023 | SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED. |
| 11/13/2023 | SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED. |
| 11/13/2023 | Please submit a separate sign permit for an signs associated with this projet. |
| 11/13/2023 | Stair Designs must be submitted and approved prior to... |
Conditions
Permit Number - TC-COM-0323-00868
Permit Status: Issued
Permit Description: NEW TRUCK TIRE AND LIGHT MECHANICAL MAINTENANCE FACILITY
| Date | Description | Comments |
|---|---|---|
| 07/28/2023 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 06/06/2025 | Prior to Issuance: This project requires issuance of a Development Package (DP) permit prior to issuance of this permit. Prior to TCO/Final: This project requires full completion of a Development Package (DP) permit prior to Temporary C of O and/or final completion this permit. | |
| 07/28/2023 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. | |
| 02/05/2025 | A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. | |
| 11/13/2023 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: Issued
Permit Number: TC-COM-0323-00868
Permite Description: NEW TRUCK TIRE AND LIGHT MECHANICAL MAINTENANCE FACILITY
Total Outstanding Inspections - 9
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/26/2025 | COT - HCPL - Rough Soil | N/A | Re-inspection required | 11-26-25: city approved plans not on site-Reschedule inspection. |
| 03/31/2026 | COT - HCEL - Electrical Intermediate | N/A | Partial Pass | 3-31-26: in wall rough electrical at room's 101, 104, 105, 106, 102, 103 verified per plans. Okay to continue with construction at progress areas. |
| 04/07/2026 | COT - HCME - Venting | N/A | Partial Pass | 4-7-26: in wall DWV & domestic approved. Okay to drywall interior side at progress areas. Note: drywall screw inspection at exterior walls with 1st layer of 5/8" approved. Okay to fire tape joints/seems. Take pictures of taping prior to installing 2nd layer of 5/8" drywall and text them to me. Screw inspection of plywood decking at mezzanine approved-okay to install 2nd layer. |
| 04/09/2026 | COT - HCPL - Gas Final | N/A | Partial Pass | 4-9-26: pe gas pressure line for exterior equipment pad verified under test and per,plans. Okay to backfill approximately 10' of open trench using shading materials. |
| 12/19/2025 | COT - HCBU - Preslab | N/A | Re-inspection required | 12/19/25: reinforcement at (3)interior spread footings must maintain 3" clearance from earth, all plumbing at slab must be wrapped to protect from concrete. |
| 12/10/2025 | COT - HCPL - Sewer | N/A | Not Ready | Courtesy inspection. 12/10/2025 |
| 05/28/2026 | COT - HCPL - Yard Water Line | N/A | Partial Pass | 5-28-26: main water line verified under test at 80psi. Okay to backfill using shading materials. |
| 06/02/2026 | COT - HCBU - Framing | N/A | Partial Pass | 6-2-26: HVAC/mechanical rough in at offices & restrooms approved. Okay to install ceiling tiles at progress areas . Also, inspected Air line pressure at 85psi. |
| 07/20/2026 | COT - HCPL - Plumbing Final | N/A | Partial Pass | 7-20-26: no hot water & submit water sterilization/chlorination report to the city for review & approval. |
Completed Inspections
Permit Status: Issued
Permit Number: TC-COM-0323-00868
Permit Description: NEW TRUCK TIRE AND LIGHT MECHANICAL MAINTENANCE FACILITY
Total Completed Inspections - 5
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2025 | COT - HCBU - Excavation/Rebar/Zoning | Passed | 10/24/25 Corrections made on the corners. |
|
| 12/02/2025 | COT - HCPL - Rough Soil | Passed | 12-2-25: underground plumbing verified under test and per plans. Okay to backfill with shading materials. | |
| 03/31/2026 | COT - HCPL - Gas Pressure Test | Passed | 3-31-26: gas pressure test approved. | |
| 05/19/2026 | COT - HCPL - Sewer | Passed | 5-19-26: final section of SDR35 PVC sewer pipe verified under test. Okay to backfill approximately 70' of open trench. | |
| 07/30/2026 | BULD - Electrical Clearance | Passed | 7-30-26: okay to meter/energize system. ECO clearance issued to TEP. |