Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address:
266 E PASTIME RD
Address NEW:
266 E PASTIME RD
Apply Date:
06/02/2010
Applicant:
N/A
Description:
ADDITION:CLASSROOM:RESTROOMS
Contractors:
  • CONCORD COMPANIES INC

Permit Reviews

Permit Number - T10CM01503
Permit Status: C of o
Permit Description: ADDITION:CLASSROOM:RESTROOMS
Start Date Submittal Complete Date Status  
04/05/2011 REVISION - - 1ST 04/05/2011 COMPLETED Review Details
06/02/2010 PLANS OK TO SUBMIT - COMM 06/02/2010 COMPLETED Review Details
06/07/2010 3RD PARTY REVIEW-COMMERCIAL TI 08/19/2010 COMPLETED Review Details
08/19/2010 POST 3RD PARTY REVIEW 08/24/2010 COMPLETED Review Details
08/24/2010 RESUBMITTAL 09/01/2010 COMPLETED Review Details
09/01/2010 RESUBMITTAL 09/09/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10CM01503
Permit Status: C of o
Permit Description: ADDITION:CLASSROOM:RESTROOMS
Total Outstanding Activity Conditions - 1
Date Name
06/02/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T10CM01503
Permit Description: ADDITION:CLASSROOM:RESTROOMS
Total Completed Inspections - 46
Date Description Inspector Results Comments
11/16/2010 PLUMBING - ROUGH, SOIL RMYERS Approved 1) PRE-SLAB 500-600 OK FOR CONCRETE
2) ROUGH SOIL FOR 300 OK TO COVER
12/01/2010 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*
1) OK HOME RUNS SE. AREA TO ELECTRIC ROOM AND CONUITS IN MASONRY WALLS EAST ROOMS
12/13/2010 BUILDING PRE-SLAB AQUIROZ Approved 1) 302-508
12/13/2010 PLUMBING - PRE SLAB RMYERS Approved IVRS - Inspection :*
12/14/2010 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
1) 4" PVC FEEDER CONDUIT FROM EXIST. SES TO CORNER OF NEW BLDG BY PALM TREE
04/12/2011 ELECTRIC - UFER RHOLLAND Approved IVRS - Inspection :*OK PVC TO CHILLER YARD & 4/0 TO REAM PLUS 40'
OK RIGID 90 DEGREES
08/03/2011 TEP CLEARANCE - AM JWEATHER Approved TEC CLEARED FOR "CHILLER METER" PER R. HOLLANDER
08/09/2011 PLUMBING - GAS PRESS TEST FNL RMYERS Approved IVRS - Inspection :*
08/09/2011 FIRE - ALARM FINAL DSIWARSKI Approved Not ready for inspection per State Fire Marshal Fred Durham.
08/09/2011 FIRE SPKLR - FINAL DSIWARSKI Approved Not ready for inspection per State Fire Marshal Fred Durham.
08/16/2011 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
08/16/2011 SHEET ROCK NAILING JBURGE Approved IVRS - Inspection :*
08/16/2011 BUILDING ABOVE CEILING JBURGE Approved IVRS - Inspection :*
08/16/2011 FRAMING JBURGE Approved IVRS - Inspection :*
08/24/2011 ELECTRIC - ABOVE CEILING RHOLLAND Approved RECEIVED CHECK #120 FOR 165.00
08/26/2011 PLUMBING - GAS RECONNECT LHANLY Approved
08/26/2011 PLUMBING - ABOVE CEILING LHANLY Approved
08/26/2011 PLUMBING - INTERMEDIATE LHANLY Approved
08/26/2011 SITE - SEWER LHANLY Approved
08/26/2011 PLUMBING - SEWER HCS CONNECT LHANLY Approved
08/26/2011 PLUMBING - GAS PRESSURE TEST LHANLY Approved
09/16/2011 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
12/28/2011 ELECTRIC - PROGRESS RHOLLAND Approved IVRS - Inspection :*
1) BOND POLE AND GEC 250.54
2) USE CORRECT SIZE LUGS
3) PROVIDE PHYSICAL PROTECTION #8 AT POLE BASE
4) VERIFY LISTING OF ELECTRIC IN GROUND PULL BOX
CHILLER:
1) LOOSE FITTINGS
2) SUPPORT SEAL TITE PER CODE
3) BOND CONTROL ENCLOSURE (NOTE INSPECTION 8/9/11)
4) 4" CONNECTOR CROSS THREADED
12/28/2011 ELECTRIC - OUTDOOR LIGHTING RHOLLAND Approved IVRS - Inspection :*
12/30/2011 ELECTRIC - FINAL LHANLY Approved ELECTRICAL INSPECTOR TO VERIFY INTERLOCK FROM RESTROOM EXHAUST FANS TO A/C
12/30/2011 BUILDING - FINAL LHANLY Approved WAITING FOR FIRE AND ELECTRICAL FINALS, EXHAUST FANS SHOULD ALSO BE INTERLOCKED TO A/C...ELECTRICAL INSPECTOR SHOULD VERIFY.
12/30/2011 BUILDING - PROGRESS LHANLY Approved
12/30/2011 REINFORCED MASONRY PRE-GROUT LHANLY Approved
12/30/2011 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved
12/30/2011 STEM WALL/RETAINING WALL LHANLY Approved
12/30/2011 MECHANICAL - FINAL LHANLY Approved
12/30/2011 MECHANICAL - HOOD SYSTEMS LHANLY Approved
12/30/2011 PLUMBING - FINAL LHANLY Approved
12/30/2011 PLUMBING - PROGRESS LHANLY Approved
01/04/2012 ELECTRIC - SERVICE UPGRADE RHOLLAND Approved IVRS - Inspection :*
01/04/2012 ELECTRIC - RECONNECT RHOLLAND Approved IVRS - Inspection :*
02/14/2012 RIGHT OF WAY - FINAL R.Hnat Approved
02/17/2012 NPPO - FINAL MRUSSO Approved
02/17/2012 SIGN - FINAL MRUSSO Approved
02/22/2012 LANDSCAPE - FINAL MRUSSO Approved
03/07/2012 FIRE SPKLR - OH PIPING & HYDRO WMOTTO Approved Approved by W. Motto on 09/20/2011 under permit #T11BU00339
03/07/2012 FIRE - KITCHEN EXH HOOD FINAL CSCHULTZ Approved No hood system was installed
03/07/2012 FIRE SPKLR - UG PIPING FLUSH CSCHULTZ Approved STATE FIRE MARSHALL OFFICE DID UNDERGROUND LINE
03/07/2012 FIRE SPKLR - UG, PIPING, HYDRO CSCHULTZ Approved STATE FIRE MARSHALL OFFICE DID UNDERGROUND LINE
03/07/2012 FIRE - FINAL CSCHULTZ Approved
06/28/2012 ENGINEERING - FINAL MRUSSO Approved