Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM01503
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALL REDO WEST LOUNGE OLD BLDG |
|
07/27/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) ANSWERED QUESTIONS ABOUT CT CAN |
|
07/26/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH WORKING AREA AT SES-OK FOR TEMP USAGE 2) NOTE: BOND RISER AND SERVICE NIPPLE 250.92 3) OK LAST 10' INTO TEP TRANSFORMER |
|
07/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DISCONNECT TO BE ACCESSIBLE ROOM 103 AND WORKING SPACE 2) JUNCTION BOXES TO BE ACCESSIBLE HALL 123 3) OK ABOVE CEILING ROOM 105 4) OK WALLS 603 & 600 |
|
07/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROVIDE PHYSICAL PROTECTION FROM SHARP METAL EDGES VDV CABLING 2) OPEN WALL ROOMS MPR FOR INSPECTION 3) EXISTING MAIN SWITHBOARD HAS CODE COMPLIANT ISSUES 110.26 (A) (1) & (2) 4) OK WALLS CLASSROOM 1,2 & 3 |
|
05/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BLDG 100 CHILLER AND OUTLETS OK |
|
04/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NO MORE THAN 360 DEGREES IN CONDUIT RUNS OK WALLS 501, 502, 505-507 |
|
03/16/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) OK LAST LIFTS 2) NEED FORMAN ON SITE |
|
03/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PVC CONDUITS 2) UNDER ELECTRIC ROOM #309 |
|
03/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/01/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK HOME RUNS SE. AREA TO ELECTRIC ROOM AND CONUITS IN MASONRY WALLS EAST ROOMS |