Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM01503
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/30/2011 | ELECTRIC - FINAL | Not ready for Inspection | ELECTRICAL INSPECTOR TO VERIFY INTERLOCK FROM RESTROOM EXHAUST FANS TO A/C | |
12/23/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/12/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
09/16/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
08/23/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 2) ROOM 600 CAP UNUSED BOXES 3) ROOM STORAGE NEEDS LIGHT 210.70, 110.26 4) RANGE NEED ANTI TIP 5) FINISH ELECTRIC ROOM 6) FINISH PREVIOUS ITEMS 1-8 7) FINISH ITEM FOR RAW SES DATED 7-21 AND 7-26 |
|
08/16/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/09/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |