Permit: T10CM01503

Parcel: 10601247B


Addresses:

266 E PASTIME RD


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T10CM01503

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/16/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
07/29/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/20/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BLDG 500 DUCT ABOVE T-BAR OK TO COVER
2) HYDRO TEST AT 100 PSI PLUS OK THRU OUT, OK TO INSULATE PIPING FROM CENTRAL PLANT TO BRAND NEW EXISTING
06/09/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) HYDRO TEST THROUGH OUT SYSTEM OUT TO CENTRAL PLANT OK 100 PSI PLUS, EXCEPT EXISTING BLDG AREA
06/03/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BLDG 100 CONDENSATE OK
2) HARD LIDS BLDG 100 OK TO COVER MECHANICAL
05/31/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/25/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RESTROOMS AT CLASSROOMS DUCT OK TO COVER
05/24/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BLDG 200 COND OK BLDG 100, AT NO TIME CAN YOU REDUE CONDENSATE PIPE SIZE
2) CONDENSATE CAN NOT RUN UP HILL (WHEEL CHAIR STORAGE)
05/16/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BLDG #300, 400 & 500 HYDRONIC ABOVE HARD LIDS INSULATION OK
05/12/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) HYDRO TEST ON REMAINING NEW BLDG MAINS OK, BRANCH TO COILS OK
05/05/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) EIGHT CLASSROOMS 200 THRU 500 OK TO COVER MECH. ONLY
2) ROOMS 306-307, CONTROL WIRING ?
3) ISSUES IN WALLS. WHERE IS CONDENSATE ?
04/20/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
HYDRO TEST ON MAIN ABOVE CEILING
UP TO BRANCH CONNETIONS OK TO INSULATE
MAINS. OK TO INSULATE UP TO COILS FROM GRID LINE "J" TO "A"
INSULATE MAINS. OK TO INS
04/01/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) HW SR AND CHWSR UP AT NEW RISERS TO NEW MECH ROOM OK, NW SR BENDS FROM BLDG TO NEW MECH ROOM OK, OK TO POUR FOOTINGS AROUND CWSR
01/26/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHW/HW S & R RISERS INTO ROOM 409
2) HYDO TEST 100 PSI AND OK, OK TO INSULATE 90 DEGREE ELLS, OK TO BACKFILL WITH PICTURES